beautypg.com

Character table – WIKA CS4L User Manual

Page 49

background image

Operating Instructions Temperature Indicating Controller CS4H / CS4L

V1.1

05/2006

- 49 -

10.3 Control

Problem

Presumed cause and solution

Process variable (tem-
perature) does not rise.

• The sensor is out of order.

Replace the sensors.

• Is sensor terminal or control output terminal securely mounted to the

instrument terminal?

Mount them securely.

• Is wiring of sensor terminal or control output terminal correct?

Wire them correctly.

If the control output
remains ON status.

• OUT1 low limit value is set to 100 % or greater in Auxiliary function set-

ting mode 2.

Set the value appropriately.

If the control output
remains OFF status.

• OUT1 high limit value is set to 0 % or less in Auxiliary function setting

mode 2.
Set the value appropriately.

If any unexplained malfunctions occur, make inquiries at our agency or us.

11. Character table

[Main setting mode]

Character Setting

item

Default

value

Data

SV1 0

°C

SV2 0

°C

[Sub setting mode]

Character Setting

item

Default

value

Data

AT setting

Cancellation

Auto-reset setting

OUT1 proportional band setting

10 °C

OUT2 proportional band setting

1.0 times

Integral time setting

200 s

Derivative time setting

50 s

ARW setting

50 %

OUT1 proportional cycle setting

30 s or 3 s

OUT2 proportional cycle setting

30 s or 3 s

A1 setting

0 °C

A2 setting

0 °C

HB (Heater burnout alarm) setting

0.0 A

LA (Loop break alarm) action time setting

0 minutes

LA (Loop break alarm) action span setting 0 °C

This manual is related to the following products: