Operating Instructions Temperature Indicating Controller CS4H / CS4L
V1.1
•
05/2006
- 49 -
10.3 Control
Problem
Presumed cause and solution
Process variable (tem-
perature) does not rise.
• The sensor is out of order.
Replace the sensors.
• Is sensor terminal or control output terminal securely mounted to the
instrument terminal?
Mount them securely.
• Is wiring of sensor terminal or control output terminal correct?
Wire them correctly.
If the control output
remains ON status.
• OUT1 low limit value is set to 100 % or greater in Auxiliary function set-
ting mode 2.
Set the value appropriately.
If the control output
remains OFF status.
• OUT1 high limit value is set to 0 % or less in Auxiliary function setting
mode 2.
Set the value appropriately.
If any unexplained malfunctions occur, make inquiries at our agency or us.
11. Character table
[Main setting mode]
Character Setting
item
Default
value
Data
SV1 0
°C
SV2 0
°C
[Sub setting mode]
Character Setting
item
Default
value
Data
AT setting
Cancellation
Auto-reset setting
OUT1 proportional band setting
10 °C
OUT2 proportional band setting
1.0 times
Integral time setting
200 s
Derivative time setting
50 s
ARW setting
50 %
OUT1 proportional cycle setting
30 s or 3 s
OUT2 proportional cycle setting
30 s or 3 s
A1 setting
0 °C
A2 setting
0 °C
HB (Heater burnout alarm) setting
0.0 A
LA (Loop break alarm) action time setting
0 minutes
LA (Loop break alarm) action span setting 0 °C