WIKA CS4L User Manual
Page 24
Operating Instructions Temperature Indicating Controller CS4H / CS4L
V1.1
•
05/2006
- 24 -
5.5 Auxiliary function setting mode 2
In the PV/SV display mode, if the MODE key is pressed while the
▲
and
▼
keys are being pressed for
approx. 3 seconds, Auxiliary function setting mode 2 can be selected.
The setting value can be increased or decreased by pressing the
▲
or
▼
key.
If the MODE key is pressed, the setting value is registered and the next setting item is selected.
If Lock 3 is selected in the Setting value lock selection, release Lock 3 to Unlock, and then change
each setting value in the Auxiliary function setting mode 2.
Sensor selection [
]
• An input type from thermocouple (10 types), RTD (2 types), DC current (2 types),
DC voltage (4 types) and the unit °C/°F can be selected.
• When changing the input from DC voltage to other inputs, remove the sensor con-
nected to this controller, then change for the input. If the input is changed with the
sensor connected, the input circuit may be broken.
• Default: K (–200 … 1370 °C)
Input type
Input range
–200 … 1370 °C:
–320 … 2500 °F:
K
–199.9 … 400.0 °C:
–199.9 … 750.0 °F:
J
–200 … 1000 °C:
–320 … 1800 °F:
R
0 … 1760 °C:
0 … 3200 °F:
S
0 … 1760 °C:
0 … 3200 °F:
B
0 … 1820 °C:
0 … 3300 °F:
E
–200 … 800 °C:
–320 … 1500 °F:
T
–199.9 … 400.0 °C:
–199.9 … 750.0 °F:
N
–200 … 1300 °C:
–320 … 2300 °F:
PL-
0 … 1390 °C:
0 … 2500 °F:
C(W/Re5-26)
0 … 2315 °C:
0 … 4200 °F:
Pt100
–199.9 … 850.0 °C:
–199.9 … 999.9 °F:
Pt100
–200 … 850 °C:
–300 … 1500 °F:
JPt100
–199.9 … 500.0 °C:
–199.9 … 900.0 °F:
JPt100
–200 … 500 °C:
–300 … 900 °F:
4 … 20 mA DC
–1999 … 9999:
0 … 20 mA DC
–1999 … 9999:
0 … 1 V DC
–1999 … 9999:
0 … 5 V DC
–1999 ... 9999:
1 … 5 V DC
–1999 … 9999:
0 … 10 V DC
–1999 … 9999:
Scaling high limit setting [
]
• Sets scaling high limit value.
• Available only for the DC input
• Setting range: Scaling low limit value to Input range high limit value
(The placement of the decimal point follows the selection.)
• Default: 9999
Scaling low limit setting [
]
• Sets scaling low limit value.
• Available only for the DC input
• Setting range: Input range low limit value to scaling high limit value
(The placement of the decimal point follows the selection.)
• Default: –1999