Operating Instructions Temperature Indicating Controller CS4H / CS4L

V1.1

05/2006

- 24 -


5.5 Auxiliary function setting mode 2

In the PV/SV display mode, if the MODE key is pressed while the

and

keys are being pressed for

approx. 3 seconds, Auxiliary function setting mode 2 can be selected.
The setting value can be increased or decreased by pressing the

or

key.

If the MODE key is pressed, the setting value is registered and the next setting item is selected.
If Lock 3 is selected in the Setting value lock selection, release Lock 3 to Unlock, and then change
each setting value in the Auxiliary function setting mode 2.

Sensor selection [

]

• An input type from thermocouple (10 types), RTD (2 types), DC current (2 types),

DC voltage (4 types) and the unit °C/°F can be selected.

When changing the input from DC voltage to other inputs, remove the sensor con-

nected to this controller, then change for the input. If the input is changed with the
sensor connected, the input circuit may be broken.

• Default: K (–200 … 1370 °C)

Input type

Input range

–200 … 1370 °C:

–320 … 2500 °F:

K

–199.9 … 400.0 °C:

–199.9 … 750.0 °F:

J

–200 … 1000 °C:

–320 … 1800 °F:

R

0 … 1760 °C:

0 … 3200 °F:

S

0 … 1760 °C:

0 … 3200 °F:

B

0 … 1820 °C:

0 … 3300 °F:

E

–200 … 800 °C:

–320 … 1500 °F:

T

–199.9 … 400.0 °C:

–199.9 … 750.0 °F:

N

–200 … 1300 °C:

–320 … 2300 °F:

PL-

0 … 1390 °C:

0 … 2500 °F:

C(W/Re5-26)

0 … 2315 °C:

0 … 4200 °F:

Pt100

–199.9 … 850.0 °C:

–199.9 … 999.9 °F:

Pt100

–200 … 850 °C:

–300 … 1500 °F:

JPt100

–199.9 … 500.0 °C:

–199.9 … 900.0 °F:

JPt100

–200 … 500 °C:

–300 … 900 °F:

4 … 20 mA DC

–1999 … 9999:

0 … 20 mA DC

–1999 … 9999:

0 … 1 V DC

–1999 … 9999:

0 … 5 V DC

–1999 ... 9999:

1 … 5 V DC

–1999 … 9999:

0 … 10 V DC

–1999 … 9999:

Scaling high limit setting [

]

• Sets scaling high limit value.
• Available only for the DC input
• Setting range: Scaling low limit value to Input range high limit value

(The placement of the decimal point follows the selection.)

• Default: 9999
Scaling low limit setting [

]

• Sets scaling low limit value.
• Available only for the DC input
• Setting range: Input range low limit value to scaling high limit value

(The placement of the decimal point follows the selection.)

• Default: –1999