Operating Instructions Temperature Indicating Controller CF2S
V1.2
•
08/2004 - 9 -
Select the sensor type by rotary switch sensor input (SW303).
Factory adjusted as K, [ ].
[Table 3.2-2]
Rotary Sw.
No.
DIP Sw.
No. 7
Type of
sensor
Scale range
0
OFF
K
-200 to 1370 °C
-320 to 2500 °F
1
OFF
J
-200 to 1000 °C
-320 to 1800 °F
2
OFF
R
0 to 1760 °C
0 to 3200 °F
3
OFF
B
0 to 1820 °C
0 to 3300 °F
4
OFF
PL-
0 to 1390 °C
0 to 2500 °F
5
OFF
N
0 to 1300 °C
0 to 2300 °F
6
OFF
Pt100
-199.9 to 850.0 °C
-199.9 to 999.9 °F
7
OFF
JPt100
-199.9 to 500.0 °C
-199.9 to 900.0 °F
0
ON
S
0 to 1760 °C
0 to 3200 °F
1
ON
E
0 to 1000 °C
0 to 1800 °F
2
ON
T
-199.9 to 400.0 °C
-199.9 to 750.0 °F
3
ON
C (W/Re5-26)
0 to 2315 °C
0 to 4200 °F
7
ON
Pt100
-200 to 850 °C
-320 to 1560 °F