WIKA CF2S User Manual
Page 39

Operating Instructions Temperature Indicating Controller CF2S
V1.2
•
08/2004 - 39 -
+2
0
12. Specifications
12.1 Standard specifications
Mounting method :
Flush
Setting
: Input system using membrane sheet key
Display
PV display
: Red LED display 4 digits, size: 8(H) x 4(W)mm
SV/MV/TIME display
: Green LED display 4 digits, size: 8(H) x 4(W)mm
Indicating accuracy
Thermocouple input
: Within ±0.3% of input range full scale ±1digit
however, for R or S input, the range 0 to 200°C (400°F), within ±6°C (12°F)
When B input, the range 0 to 300°C (600°F), accuracy is not guaranteed.
When K, J, T input, the range less than 0°C (32°F),
within ±0.5% of full scale ±1digit
(Cold junction compensating accuracy, ±1°C, at 0 to 50°C)
RTD input
: Within ±0.3% of input range full scale ±1digit
Setting accuracy
: The same as indicating accuracy
Input sampling period
: 0.125 seconds
Input
Thermocouple
: K, J, R, S, B, E, T [JIS, IEC], C (W/Re5-26) [ASTM],
N (IEC) and PL-ll (NBS)
External resistance, 100
Ω or less
In the case of input burnout, Upscale
RTD
: Pt100 (JIS, IEC), JPt100, 3-wire system
Allowable input lead wire resistance 10
Ω or less per wire
In the case of input burnout, Upscale
Control output
Relay contact
: 1a
Control capacity, 250Vac 3A (resistive load)
250Vac 1A (inductive load cosø=0.4)
Non-contact voltage
: For SSR drive
12 VDC maximum 40mA DC (short circuit protected)
Current
: 4 to 20mA DC (Isolated type)
Load resistance, maximum 550
Ω