Operating Instructions Temperature Indicating Controller CF2S
V1.2
•
08/2004 - 20 -
Main output ON/OFF
Mode to set the ON/OFF action hysteresis of the
action hysteresis setting
main control output.
Setting value
Setting range: 0.1 to 100.0°C
[Factory adjusted as 1.0°C]
This display is indicated only when the ON/OFF action
is designated in Control action designation (page10).
Alarm 1 (A1) action
Mode to select the action Energized or Deenergized
Energized/Deenergized
for Alarm 1.
Selection
[Factory adjusted as Energized]
This display is not indicated when the rotary switch is set to No. 0
or No. 7 in Alarm 1 action designation (page 12).
Energized
Deenergized
Alarm 2 (A2) action
Mode to select the action Energized or Deenergized
Energized/Deenergized
for Alarm 2.
Selection
[Factory adjusted as Energized]
This display is not indicated when the rotary switch is set to
No. 0 or No. 7 in Alarm 2 action designation (page 14), or
the option [2AS] or [2AL] is not applied.
Selection items: The same as those of the alarm 1 (A1) action
Energized/Deenergized selection.
Alarm 1 hysteresis setting
Mode to set the hysteresis value for Alarm 1.
Setting value
Setting range: 0.1 to 100.0°C
[Factory adjusted as 1.0°C]
This display is not indicated when the rotary switch is set to
No. 0 or No. 7 in Alarm 1 action designation (page 12).
Alarm 2 hysteresis setting
Mode to set the hysteresis value for Alarm 2.
Setting value
Setting range: 0.1 to 100.0°C
[Factory adjusted as 1.0°C]
This display is not indicated when the option [2AS] or [2AL]
is not applied and when the rotary switch is set to No. 0
or No. 7 in Alarm 2 action designation (page 12) even
if the option [2AS] or [2AL] is applied.