WIKA CF2S User Manual
Page 21
Operating Instructions Temperature Indicating Controller CF2S
V1.2
•
08/2004 - 21 -
Alarm 1 (A1) action
Mode to set the action delayed timer for Alarm 1.
delayed timer setting
Setting range: 0 to 9999s
Setting value
[Factory adjusted as 0s]
Alarm output is turned on when the setting time has passed
after the input gets into the alarm output range.
This display is not indicated if the rotary switch is set to
No. 0 or No. 7 in Alarm 1 action designation (page 12).
Alarm 2 (A2) action
Mode to set the action delayed timer for Alarm 2.
delayed timer setting
Setting range: 0 to 9999s
Setting value
[Factory adjusted as 0s]
Alarm output is turned on when the setting time has passed
after the input gets into the alarm output range.
This display is not indicated when the option [2AS] or [2AL] is
not applied and when the rotary switch is set to No. 0 or
No. 7 in Alarm 2 action designation even if the option [2AS]
or [2AL] is applied (P.12).
Display selection when
Mode to select the display when the control output
control output is off
is off.
Selection
[Factory adjusted as indicating OFF on the PV display]
OFF is indicated on the PV display.
No indication (all unlit).
Only PV is indicated.
Main setting value
Mode to set the rising rate of the main setting
rising rate setting
value. (Rising value per minute)
Setting value
Setting the value to 0 or 0.0 disables the function.
Setting range:
0 to 9999°C /min. Thermocouple, except T and RTD without a decimal point
0.0 to 999.9°C /min. Thermocouple T and RTD with a decimal point
[Factory adjusted as 0°C /min.]
Main setting value
Mode to set the falling rate of the main setting
falling rate setting
value. (Falling value per minute)
Setting value
Setting the value to 0 or 0.0 disables the function.
Setting range:
0 to 9999°C /min. Thermocouple, except T and RTD without a decimal point
0.0 to 999.9°C /min. Thermocouple T and RTD with a decimal point
[Factory adjusted as 0°C /min.]
PV/SV display mode
Actual Main setting
temperature value