WIKA CF2S User Manual
Page 46
Operating Instructions Temperature Indicating Controller CF2S
V1.2
•
08/2004 - 46 -
14. Character table
Character
Item
Initial value
Data
Main setting
0°C
Character
Item
Initial value
Data
Setting value memory number
1
Auto-tuning Perform/Cancel
- - - -: Cancel
Proportional band
2.5%
Integral time setting
200s
Derivative time setting
50s
Proportional cycle
R/M: 30s
S/M: 3s
Manual reset setting
0.0°C
Alarm 1 setting
0°C
Alarm 2 setting
0°C
Loop break alarm time setting
0 minutes
Loop break alarm span setting
0°C
Character
Item
Initial value
Data
Setting value lock designation
- - - -: Unlock
Main setting value high limit
400°C
Main setting value low limit
0°C
Sensor correction setting
0.0°C
Instrument number setting
0
Transfer rate selection
9600bps
Communication protocol
selection
:
WIKA
standard protocol
Character
Item
Initial value
Data
Scaling high limit setting
1370°C
Scaling low limit setting
-200°C
PV filter time constant
0.0 seconds
Main output high limit setting
100%
Main output low limit setting
0%
Main output ON/OFF action
hysteresis
1.0°C
Alarm 1 action Energized/Deenergized
: Energized
Alarm 2 action Energized/Deenergized
: Energized
Alarm 1 hysteresis setting
1.0°C
Alarm 2 hysteresis setting
1.0°C
Alarm 1 delayed timer setting
0 seconds
Alarm 2 delayed timer setting
0 seconds
Display selection when control
output is off
Main setting value rising rate
0°C/minute
Main setting value falling rate
0°C/minute