WIKA operating instructions model TGT73

9.2 Cleaning

CAUTION!

Clean the instrument with a moist cloth.

Wash or clean the dismounted instrument before

returning it in order to protect personnel and the

environment from exposure to residual media.

Residual media in the dismounted gas-actuated

thermometer can result in a risk to personnel,

the environment and equipment. Take sufficient

precautionary measures.

For information on returning the instrument see chapter

11.2 "Return".

10. Faults

Faults

Causes

Measures

No output signal

No power supply or

cable break

Check voltage supply

and cables. Replace any

defective components found

Transmitter incorrectly

connected

Check connections; correct

connections if necessary

Electronics failure due to

too high power supply or

through external voltage

Return the instrument to the

manufacturer for repair

Constant output

signal upon change in

temperature

Power supply connected

the wrong way

(I = approx. 4.5 mA)

Check connection, and if

necessary, swap terminals

1 and 2

Transmitter fault

Return the instrument to the

manufacturer for repair

Too high, constant

output signal upon

change in temperature

Electronics failure due to

too high power supply or

through external voltage

Return the instrument to the

manufacturer for repair

Signal span too small Power supply too low

Rectify the power supply

Load too high

Stay within the max.

permissible load