WIKA operating instructions pressure transmitter, model S-11

GB

14043046.01 06/2012 GB/D/F/E

6. Commissioning, operation

6.1 Mechanical mounting

Remove the protection cap not until shortly before installation.

Ensure that the diaphragm of the process connection is not damaged

during installation.

The sealing faces at the pressure transmitter and the measuring point

always have to be clean.

Only ever screw in, or unscrew, the instrument using the spanner

flats. Never use the case or the cooling element as a working surface.

The correct torque depends on the dimensions of the process

connection and the gasket used (form/material).

When screwing in, do not cross the threads.

For information on tapped holes and welding sockets, see Technical

information IN 00.14 at www.wika.com.

Attach the connector and screw it in hand-tight. The assembly of the

angular connector is described in chapter 6.2 "Electrical mounting".

Sealing

Correct sealing of the process

connections with parallel threads

at the sealing face

must be

made using suitable flat gaskets,

sealing rings or WIKA profile

sealings. The sealing of tapered

threads (e.g. NPT threads) is

made by providing the thread with

additional sealing material such as, for example, PTFE tape (EN 837-2).

For further information on seals see WIKA data sheet AC 09.08 or under www.wika.com.

Spanner flats

Parallel thread

Tapered thread

per EN 837

per DIN 3852-E

NPT, R and PT