beautypg.com

Comfort-Aire HBH Series 1/2 to 5 Ton User Manual

Page 33

background image

Heat Controller, Inc.

HBH/V COMPACT

IOM Instructions

Unit Start-up Procedure

1. Turn the thermostat fan position to “ON”. Blower

should start.

2. Balance air flow at registers.

3. Adjust all valves to their full open positions. Turn on

the line power to all heat pumps.

4. Room temperature should be within the minimum-

maximum ranges of table 6. During start-up checks,

loop water temperature entering the heat pump

should be between 60°F [16°C] and 95°F [35°C].

5. Two factors determine the operating limits of Heat

Controller heat pumps, (a) return air temperature, and (b)

water temperature. When any one of these factors is at a

minimum or maximum level, the other factor must be at

normal level to insure proper unit operation.

a. Adjust the unit thermostat to the warmest setting.

Place the thermostat mode switch in the “COOL”

position. Slowly reduce thermostat setting until the

compressor activates.

b. Check for cool air delivery at the unit grille within a

few minutes after the unit has begun to operate.

Note: Units have a five minute time delay in the

control circuit that can be eliminated on the CXM

control board as shown below in Figure 23. See

controls description for details.

c. Verify that the compressor is on and that the water

flow rate is correct by measuring pressure drop

through the heat exchanger using the P/T plugs

and comparing to tables 10.

d. Check the elevation and cleanliness of the

condensate lines. Dripping may be a sign of a

blocked line. Check that the condensate trap is

filled to provide a water seal.

e. Refer to table 9. Check the temperature of both

entering and leaving water. If temperature is within

range, proceed with the test. If temperature is

outside of the operating range, check refrigerant

pressures and compare to tables 8a through

8d. Verify correct water flow by comparing unit

pressure drop across the heat exchanger versus

the data in tables 7. Heat of rejection (HR) can

be calculated and compared to submittal data

capacity pages. The formula for HR for systems

with water is as follows:

HR (Btuh) = TD x GPM x 500, where TD is the

temperature difference between the entering and

leaving water, and GPM is the flow rate in U.S.

GPM, determined by comparing the pressure drop

across the heat exchanger to table 7. In S.I. units,

the formula is as follows: HR (kW) = TD x l/s x

4.18.

f. Check air temperature drop across the air coil when

compressor is operating. Air temperature drop

should be between 15°F and 25°F [8°C and 14°C].

g. Turn thermostat to “OFF” position. A hissing noise

indicates proper functioning of the reversing valve.

6. Allow five (5) minutes between tests for pressure to

equalize before beginning heating test.

a. Adjust the thermostat to the lowest setting. Place

the thermostat mode switch in the “HEAT” position.

b. Slowly raise the thermostat to a higher

temperature until the compressor activates.

c. Check for warm air delivery within a few minutes

after the unit has begun to operate.

d. Refer to table 9. Check the temperature of both

entering and leaving water. If temperature is within

range, proceed with the test. If temperature is outside

of the operating range, check refrigerant pressures

and compare to tables 8a through 8d. Verify correct

water flow by comparing unit pressure drop across the

heat exchanger versus the data in tables 8a through

8d. Heat of extraction (HE) can be calculated and

compared to submittal data capacity pages. The

formula for HE for systems with water is as follows:

HE (Btuh) = TD x GPM x 500, where TD is the

temperature difference between the entering and

leaving water, and GPM is the flow rate in U.S.

GPM, determined by comparing the pressure drop

across the heat exchanger to tables 10a through

10e. In S.I. units, the formula is as follows: HE

(kW) = TD x l/s x 4.18.

e. Check air temperature rise across the air coil when

compressor is operating. Air temperature rise should

be between 20°F and 30°F [11°C and 17°C].

f. Check for vibration, noise, and water leaks.

7. If unit fails to operate, perform troubleshooting analysis

(see troubleshooting section). If the check described

fails to reveal the problem and the unit still does not

operate, contact a trained service technician to insure

proper diagnosis and repair of the equipment.

8. When testing is complete, set system to maintain

desired comfort level.

9.

BE CERTAIN TO FILL OUT AND FORWARD ALL WARRANTY
REGISTRATION PAPERS TO HEAT CONTROLLER.

Note: If performance during any mode appears abnormal,

refer to the CXM section or troubleshooting section of

this manual. To obtain maximum performance, the air

coil should be cleaned before start-up. A 10% solution of

dishwasher detergent and water is recommended.

Unit Start-Up Procedure

This manual is related to the following products: