Comfort-Aire HBH Series 1/2 to 5 Ton User Manual
Page 22

IOM Instructions
HBH/V COMPACT
Heat Controller, Inc.
HB
Model
Voltage
Code
Rated
Voltage
Voltage
Min/
Max
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amp
Max
Fuse/
HACR
QTY RLA LRA
015
1
208-230/60/1
197/254
1
6.0
29.0
1.00
7.0
8.5
15
8
265/60/1
239/292
1
5.4
28.0
0.86
6.3
7.6
15
018
1
208-230/60/1
197/254
1
7.2
33.0
1.50
8.7
10.5
15
8
265/60/1
239/292
1
5.9
28.0
1.30
7.2
8.7
15
024
1
208-230/60/1
197/254
1
12.8
58.3
3.00
15.8
19.0
30
8
265/60/1
239/292
1
9.6
54.0
2.70
12.3
14.7
20
030
1
208-230/60/1
197/254
1
14.1
73.0
3.00
17.1
20.6
30
8
265/60/1
239/292
1
11.2
60.0
2.70
13.9
16.7
25
3
208-230/60/3
197/254
1
8.9
58.0
3.00
11.9
14.1
20
4
460/60/3
414/506
1
4.2
28.0
1.70
5.9
7.0
15
036
1
208-230/60/1
197/254
1
16.7
79.0
3.00
19.7
23.9
40
8
265/60/1
239/292
1
13.5
72.0
2.70
16.2
19.6
30
3
208-230/60/3
197/254
1
10.4
73.0
3.00
13.4
16.0
25
4
460/60/3
414/506
1
5.8
38.0
1.70
7.5
9.0
15
042
1
208-230/60/1
197/254
1
17.9
112.0
3.00
20.9
25.4
40
3
208-230/60/3
197/254
1
13.5
88.0
3.00
16.5
19.9
30
4
460/60/3
414/506
1
6.0
44.0
1.70
7.7
9.2
15
5
575/60/3
518/633
1
4.9
34.0
1.40
6.3
7.5
15
048
1
208-230/60/1
197/254
1
21.8
117.0
4.90
26.7
32.2
50
3
208-230/60/3
197/254
1
13.7
83.1
4.90
18.6
22.0
35
4
460/60/3
414/506
1
6.2
41.0
2.50
8.7
10.3
15
5
575/60/3
518/633
1
4.8
33.0
1.90
6.7
7.9
15
060
1
208-230/60/1
197/254
1
26.3
134.0
5.80
32.1
38.7
60
3
208-230/60/3
197/254
1
15.6
110.0
5.80
21.4
25.3
40
4
460/60/3
414/506
1
7.8
52.0
2.60
10.4
12.4
20
5
575/60/3
518/633
1
5.8
38.9
2.30
8.1
9.6
15
HACR circuit breaker in USA only
All fuses Class RK-5
Table 4b: HB Series Electrical Data - (Standard 60Hz Units High Static)