beautypg.com

Cxm pcb, Caution, Electrical - low voltage wiring – Comfort-Aire HBH Series 1/2 to 5 Ton User Manual

Page 25: Water valve wiring

background image

Heat Controller, Inc.

HBH/V COMPACT

IOM Instructions

Figure 18: FP1 Limit Setting

CXM PCB

JW3-FP1

jumper should

be clipped for

low temperature

operation

Accessory Connections

A terminal paralleling the compressor contactor coil

has been provided on the CXM control. Terminal “A”

is designed to control accessory devices, such as

water valves. Note: This terminal should be used only

with 24 Volt signals and not line voltage. Terminal

“A” is energized with the compressor contactor.

See Figure 19 or the specific unit wiring diagram for

details.

Figure 19: Accessory Wiring

Water Solenoid Valves

An external solenoid valve(s) should be used on ground

water installations to shut off flow to the unit when the

compressor is not operating. A slow closing valve may be

required to help reduce water hammer. Figure 19 shows

typical wiring for a 24VAC external solenoid valve. Figures

20 and 21 illustrate typical slow closing water control valve

wiring for Taco 500 series and Taco ESP series valves.

Slow closing valves take approximately 60 seconds to

open (very little water will flow before 45 seconds). Once

fully open, an end switch allows the compressor to be

energized. Only relay or triac based electronic thermostats

should be used with slow closing valves. When wired as

shown, the slow closing valve will operate properly with

the following notations:

1. The valve will remain open during a unit lockout.

2. The valve will draw approximately 25-35 VA through

the “Y” signal of the thermostat.

Note: This valve can overheat the anticipator of an

electromechanical thermostat. Therefore, only relay or

triac based thermostats should be used.

Low Voltage VA Ratings

Component

VA

Typical Blower Relay

6 - 7

Typical Reversing Valve Solenoid

4 - 6

30A Compressor Contactor

6 - 9

Subtotal

16 - 22

+ CXM board (5 - 9 VA)*

21 - 31

Remaing VA for Accessories

19 - 29

*Standard transformer for CXM board is 50VA.

Electrical - Low Voltage Wiring

Figure 20: Taco 500 Series Valve Wiring

Figure 21: Taco SBV Valve Wiring

C

C

Termostato

Y

1

2

3

Y

AVM

Taco Válvula

Calentador Interruptor

Unidad Empacada

C

C

Thermostat

Y1

1

2

3

Y1

AVM

Taco Valve

Heater Switch

CAUTION!

CAUTION! Many units are installed with a factory or field

supplied manual or electric shut-off valve. DAMAGE WILL

OCCUR if shut-off valve is closed during unit operation. A high

pressure switch must be installed on the heat pump side of

any field provided shut-off valves and connected to the heat

pump controls in series with the built-in refrigerant circuit high

pressure switch to disable compressor operation if water

pressure exceeds pressure switch setting. The field installed

high pressure switch shall have a cut-out pressure of 300 psig

and a cut-in pressure of 250 psig.

Water Valve Wiring

This manual is related to the following products: