beautypg.com

Comfort-Aire HBH Series 1/2 to 5 Ton User Manual

Page 12

background image

IOM Instructions

HBH/V COMPACT

Heat Controller, Inc.

Vertical Installation

Sound Attenuation for Vertical Units

Sound attenuation is achieved by enclosing the unit within a

small mechanical room or a closet. Additional measures for

sound control include the following:

1. Mount the unit so that the return air inlet is 90° to the

return air grille. Refer to Figure 9. Install a sound baffle as

illustrated to reduce line-of sight sound transmitted through

return air grilles.

2. Mount the unit on a rubber or neoprene isolation pad to mini-

mize vibration transmission to the building structure.

Figure 9: Vertical Sound Attenuation

Condensate Piping – Vertical Units

Vertical units utilize a condensate hose inside the cabinet as

a trapping loop; therefore an external trap is not necessary.

Figure 10a shows typical condensate connections. Figure 10b

illustrates the internal trap for a typical vertical heat pump.

Each unit must be installed with its own individual vent (where

necessary) and a means to flush or blow out the condensate

drain line. Do not install units with a common trap and/or vent.

Vent

*3/4" IPT

3/4" PVC

Alternate

Condensate

Location

Water

Connections

(21mm per m)

* Some units include a painted drain connection. Using a

threaded pipe or similar device to clear any excess paint

accumulated inside this fitting may ease final drain line installation.

Figure 10a: Vertical Condensate Drain

Figure 10b: Vertical Internal Condensate Trap

NOTICE! Units with clear plastic drain lines should have

regular maintenance (as required) to avoid buildup of debris,

especially in new construction.

This manual is related to the following products: