Figure 4 Note: Allow for ceiling thickness.

Suggested Installation: Unit with filter.

3 Phase, 9 Lead Motor Y-Connection

4 5 6

1

7

2

8

3

9

L1 L2 L3

4 5 6

7 8 9

1 2 3

L1 L2 L3

Low Voltage

208/230 Volts

High Voltage

460 Volts

3 Phase, 9 Lead Motor

Y-Connection

To reverse, interchange any 2 line leads.

3 Phase, 9 Lead Motor Delta-Connection

7

1

6

7 8 9

4 5 6

1 2 3

Low Voltage

208/230 Volts

High Voltage

460 Volts

8

2

4

9

3

5

L1

L3

L2

L1

L3

L2

3 Phase, 9 Lead Motor

Delta-Connection

To reverse, interchange any 2 line leads.

2 Speed, 1 Winding, 3 Phase Motor

Motor

1

2

3

4
5

6

Together

High Speed

Line

L1

L2

L3

1

2

3

4
5

6

Open

Low Speed

Line

L1

L2

L3

Motor

To reverse, interchange any 2 line leads. Motors

require magnetic control.

2 Speed, 2 Winding, 3 Phase

To reverse: High Speed-interchange leads T11 and

T12.
Low Speed-interchange leads T1 and T2. Both

Speeds-interchange any 2 line leads.

Single Speed, Single Phase Motor

T-1
T-4

Ground B

L 2

L1

Ground A

Line

When ground is required, attach to ground A or B with

no. 6 thread forming screw. To reverse, interchange

T-1 and T-4.

2 Speed, 2 Winding, Single Phase Motor

Ground A

Ground B

T-1

T-4

Low Speed

High Speed

L1

L2

Line

When ground required, attach to ground A or B with

No. 6 thread forming screw. To reverse, interchange

T-1 and T-4 leads.

Single Speed, Single Phase, Dual Voltage

Ground B

J-10

T-5

Ground A

Link A
Link B

Low Voltage

Line

L 2

L 1

Ground A

Link A & B

L1

L2

Line

Ground B

T-5

J-10

When ground required, attach to ground A or B with

No. 6 thread forming screw. To reverse, interchange

T-5 and J-10 leads.

Typical Damper Motor Schematic

Fan

Motor

Damper

Motor*

Second

Damper

Motor

Transformer**

Transformer**

L3

L2

L1

For 3 phase, damper motor voltage should be

the same between L1 and L2. For single phase

application, disregard L3. *Damper motors may be

available in 115, 230 and 460 volt models. The damper

motor nameplate voltage should be verified prior to

connection. **A transformer may be provided in some

installations to correct the damper motor voltage to the

specified voltage.