Alt a, Enabled – Hellenbrand H-125 Series User Manual

Page 16

background image

16

30:00

RECLAIM START
SET

MIN

8:00

RECLAIM DURATION
SET

MIN

Step 5CS

Only displays if reclamation of brine is enabled in Step 3CS. Selection requires that a connec-

tion to a MAV is made to the two-pin connector labeled DRIVE on PC Board.

Press NEXT to go to Step 4CS. Press REGEN to return to previous step.

STEP 4CS – Use the  or  buttons to select the number of minutes after the start of the draw

cycle before the MAV will divert the brine waste water from the plumbing drain receptacle to the

brine tank. Press NEXT to select duration of brine reclaim.

STEP 5CS – Only displays if reclamation of brine is enabled in Step 3CS. Use the  or  but-

tons to select the number of minutes to divert the brine waste water to the brine tank. After the

minutes count down to zero the waste water will once again be diverted to the plumbing drain

receptacle.

Press NEXT to go to Step 8CS. Press REGEN to return to previous step.

STEP 6CS –Twin Alternating System – Allows automatic alternation between two units to

provide softened water 24 hours a day.

Use  or  buttons to select ALT A or ALT B. Selection requires connection to a MAV is made.

Select ALT A for the control valve that has the two pin connector labeled DRIVE connected to

the MAV (motorized alternator valve).

Select ALT B for the control valve that will not be connected to the alternator valve motor.

Must do one of the following:

• If set up for a softener, Volume Capacity in GALLONS, select

Regeneration Time Option “IMMEDIATE” and select DAYS BETWEEN REGEN “OFF”.

• For additional programming information, refer to MAV manual.

Press NEXT to go to Step 8CS. Press REGEN to return to previous step.

STEP 7CS – No Hard Water Bypass Enabled - Use  or  buttons to select NO HARD

WATER BYPASS ENABLE. Selection requires that a connection to a Motorized Alternator Valve

(MAV) is made to the two pin connector labeled ALTERNATOR DRIVE located on the printed

circuit board. The MAV will be driven closed before the first regeneration cycle that is not FILL

or SOFTENING or FILTERING, and be driven open after the last regeneration cycle that is not

FILL.

Press NEXT to go to Step 8CS. Press REGEN to return to previous step.

ENABLED

RECLAMATION MODE
SET

Step 4CS

ENABLED

NO HARD BYPASS
SET

Step 7CS

ALT A

ALTERNATOR SYSTEM
SET

Step 6CS