beautypg.com

Blodgett CB-E SERIES User Manual

Page 8

background image

8

3.0 OPERATING INSTRUCTIONS

For CSD-1 equipped boilers, see section 4.0 CSD-1 Optional Feature for proper
operating instructions.

BOILER CONTROLS (Inside Cabinet)

Main Power Switch

- ON fills the boiler tank and turns the boiler heaters on. You

should allow 20 minutes to fill the tank and generate steam.


- OFF shuts off the boiler heaters and opens the Automatic

Blowdown Valve, emptying the boiler tank and releasing
water and steam to the drain. This should be done daily to
remove sediment, lime, or scale.

Pilot Light

- Indicates main power is ON.


Boiler Pressure Gauge

- Should read 9 - 11 psig during operation; 0 psig during

shutdown.


Water Level Sight Glass - Observe level of water and water quality in the boiler.

Murkiness in the water indicates inadequate water quality;
the owner must supply proper water to the boiler (see page
4).


Water Level Control

- While boiler is ON, briefly open the water level control valve

once a day to remove any sediment that might accumulate.
(See page 11 for detailed instructions.)


Safety Valve

- This valve will release (pop off) if the boiler has too much

pressure. Once a week, this valve should be tripped during
operation to make sure it functions properly.


OPERATION OF THE BOILER

Turn on water and power supply.

Open cabinet door and turn main power switch ON. Pilot light ignites and water begins
to fill boiler - observe water gauge sight glass to verify that proper water level is reached.

Once the proper water level is reached, the heaters begin to heat the water. Heaters
require about 15 minutes to begin steam generation. The boiler pressure gauge in the
cabinet should indicate steam pressure in a range of 9 to 11 psig.

SHUT DOWN

Turn the Main Power Switch OFF: Open manual drain valve. If unit is supplied with
Automatic Blowdown Valve, it will open, draining the boiler and releasing hot water and
steam to the drain.