Options/accessories – APC SILCON 10-40KW 400V UPS User Manual

Page 55

background image

Options/Accessories

990-4050

Installation Guide APC Silcon 10-40kW 400V UPS

55

***

If no external System Output fuses are available or if it has a higher value than
indicated above, System Output and UPS Output cables should be dimensioned as
System Input and UPS Input cables.

**

Sizes according to IEC 364-5-532 for PVC insulated copper cables (max. ambient
temperature: 30

o

C). Installation method B: Insulated conductors in wall conduit.

Also refer to local legal regulations.

Beware that single-phase Switch Mode Power supply loads will increase neutral
current! At a 100% SMPS load, neutral cable should be dimensioned for 200% of
phase current.

*

Depth of enclosure includes switch handles

Main supply

Load

Service
Bypass
Panel

APC Silcon UPS

Signalling

10 x 0.75mm

2

(max. 2mm

2

)

O/P I/P SBP