Installation Guide APC Silcon 10-40kW 400V UPS

990-4050

Programming Parameters

5.0 Programming Parameters

Below table shows operating parameters programmable from keyboard. Only qualified users
should re-set programming parameters.

5.1

Parameters

* Factory settings in bold

** Only for systems with Battery Monitor active

*** Do not leave system running in bypass mode (Static bypass) for extended periodes of time,
as batteries are not recharged in bypass mode.

Parameter

Setting*

Comments

Bypass operation

YES, NO

YES will switch the system into bypass mode

Language

GB, D, F
DK, S, SF
NL, PL, CZ
E, P, SK, H

Language of text in display

Autostart

YES, NO

Automatic restart by mains return
(1 min.delay). Ensures quick battery recharge

Remote shutdown active

YES, NO

Shutdown of UPS by remote signal when in
battery operation. Saves battery energy

Remote shutdown

HIGH, LOW

Nature of remote shutdown signal level

Remote shutdown time

0, 1, 2, 3, 4
5, 6, 7, 8, 9
10 min.

Time delay on remote shutdown of UPS

Battery capacity test

---

Initiates back-up time check.
Time measured from start until it reaches low
DC warning level.
(See User Guide section 6 )

Battery monitor test**

---

Initiates checks of battery condition by 25%
discharging

Automatic battery test**

OFF, 3, 6 months

Activates the battery monitor test in cyclic
intervals

Battery monitor reset**

---

Press the

and

key


to resets alarm (flashing light)!

Boost charge

YES, NO

YES results in boost charge (10 hours)

Autoboost charge

YES, NO

YES results in boost charge after battery
operation. (10 hours)

Enter new date

YYMMDD

Set tolocal date

Enter new time

HHMMSS

Set to local time (24 hour clock)