Programming parameters, 0 programming parameters – APC SILCON 10-40KW 400V UPS User Manual
Page 46
46
Installation Guide APC Silcon 10-40kW 400V UPS
990-4050
Programming Parameters
5.0 Programming Parameters
Below table shows operating parameters programmable from keyboard. Only qualified users
should re-set programming parameters.
5.1
Parameters
* Factory settings in bold
** Only for systems with Battery Monitor active
*** Do not leave system running in bypass mode (Static bypass) for extended periodes of time,
as batteries are not recharged in bypass mode.
Parameter
Setting*
Comments
Bypass operation
YES, NO
YES will switch the system into bypass mode
Language
GB, D, F
DK, S, SF
NL, PL, CZ
E, P, SK, H
Language of text in display
Autostart
YES, NO
Automatic restart by mains return
(1 min.delay). Ensures quick battery recharge
Remote shutdown active
YES, NO
Shutdown of UPS by remote signal when in
battery operation. Saves battery energy
Remote shutdown
HIGH, LOW
Nature of remote shutdown signal level
Remote shutdown time
0, 1, 2, 3, 4
5, 6, 7, 8, 9
10 min.
Time delay on remote shutdown of UPS
Battery capacity test
---
Initiates back-up time check.
Time measured from start until it reaches low
DC warning level.
(See User Guide section 6 )
Battery monitor test**
---
Initiates checks of battery condition by 25%
discharging
Automatic battery test**
OFF, 3, 6 months
Activates the battery monitor test in cyclic
intervals
Battery monitor reset**
---
Press the
and
key
to resets alarm (flashing light)!
Boost charge
YES, NO
YES results in boost charge (10 hours)
Autoboost charge
YES, NO
YES results in boost charge after battery
operation. (10 hours)
Enter new date
YYMMDD
Set tolocal date
Enter new time
HHMMSS
Set to local time (24 hour clock)