beautypg.com

External connection – APC SILCON 10-40KW 400V UPS User Manual

Page 43

background image

External Connection

990-4050

Installation Guide APC Silcon 10-40kW 400V UPS

43

4.8.3 Fuse-box

UPS

Ampere Rating

[A]

Connection

Cable [mm

2

]

Max.

short-circuit

current [kA]

Dimensions

HxWxD [mm]

Weight

[kg]

10 kW
20 kW
40 kW

25
50
63

4
10
16

10
10
10

540x540x183
504x540x183
540x540x183

20
20
20