beautypg.com

External connection – APC SILCON 10-40KW 400V UPS User Manual

Page 41

background image

External Connection

990-4050

Installation Guide APC Silcon 10-40kW 400V UPS

41

4.8.1 Battery Breaker Box

UPS

Ampere

Rating

[A]

Connection

Cable

[mm2]

Max.

short-

circuit

current [kA]

Dimensions

HxWxD [mm]

Weight

[kg]

10 kW
20 kW
40 kW

25
50
63

4
10
16

10
10
10

540x540x183
504x540x183
540x540x183

20
20
20