The HC2S3 draws approximately 2 mA powered from 12V. The HC2S3 can
be continuously powered from the 12V terminal, or power can be switched
with the SW12V terminal to conserve battery life. When power is switched, a
three-second warm-up time is required. Using the SW12V terminal on the
CR10X datalogger requires a user-supplied jumper wire connected between the
SW 12V CTRL terminal and a Control Port (C1 to C8).

When measuring the HC2S3 with single-ended
measurements, the yellow and gray leads must both be
connected to AG on the CR10(X) and CR500/CR510 or to

on the CR1000, CR5000, and CR23X. Doing otherwise

will connect the datalogger’s analog and power ground
planes to each other, which in some cases can cause
offsets on low-level analog measurements. To avoid 2 mA
flowing into analog ground, switch power on/off for its
measurement.

CAUTION

TABLE 7-1. Connections for Single-Ended Measurements




Color




Description

CR1000,
CR3000,

CR800,

CR5000,

CR23X

CR10X

CR10,

CR510,

CR500

Brown Temperature

Signal

Single-Ended

Input

Single-Ended

Input

White Relative

Humidity

Signal

Single-Ended

Input

Single-Ended

Input

Yellow Signal

Reference

AG

Gray Power

Ground

AG

Clear Shield

G

Green Power

12V/*SW12V

12V/*SW12V

*CR10X Power Control if

using SW 12V

Jumper

from

SW 12V

CTRL to

Control Port

12