Model, 24 v, 97 vac ~ 123 vac – Samlex America SR1000-148 User Manual
Page 24: 47 hz ~ 63 hz, Sr series inverter
SR Series Inverter
23
Model
Setting Value Range
24 V
23 VDC ~ 27 VDC
48 V
46 VDC ~ 54 VDC
10). UV Alarm: Sets Under Voltage (UV) alarm. When the input voltage is
lower than the set value, the unit will sound “beep” to remind
that the unit is going to shutdown. At the meantime, the
contact in the internal Dry Contact Relay will open / close
(See details in Section 3-1-6).
Default= 21 VDC for 24 V Model, 42 VDC for 48 V Model
Model
Setting Value Range
24 V
19 VDC ~ 23 VDC
48 V
38 VDC ~ 46 VDC
NOTE. The value of voltage set for the “UV Alarm” should be equal to or
higher than the value set for “UVP” or else the unit will shutdown
without any audible warning.
5-3-3. O/P Parameters:
11). O/P Voltage: Set the inverter output voltage.
Default= 110 VAC for 110 V Model, 230 VAC for 220 V Model
Model
Setting Value Range
110 V
97 VAC ~ 123 VAC
220 V
194 VAC ~ 246 VAC
12). O/P Frequency: Set the inverter output frequency.
Default= 60 Hz for 110 V Model, 50 Hz for 220 V Model.
Model
Setting Value Range
110 V
47 Hz ~ 63 Hz
220 V
47 Hz ~ 63 Hz
13). Sync Frequency: Sets the AC output synchronous frequency.
Example: AC input= 230 VAC / 50Hz,User setting Value= 7Hz
When the DC to AC inverter “Frequency” is
within The Range of 43 Hz~57 Hz, the internal
bypass relay will
operate normally. When the
“Frequency” is less than 43 Hz or more than 58 Hz,
the internal bypass relay will de-energize.
(See details in Section 2-2)
Default= 0.1Hz ~ 7Hz.
Model
Setting Value Range
110 V
0.1 Hz ~ 7 Hz
230 V
0.1 Hz ~ 7 Hz