Sr series inverter – Samlex America SR1000-148 User Manual
Page 11
SR Series Inverter
10
1). Before installing the inverter, ensure that the main switch “OFF”.
2). Before using the remote function, ensure that the main switch pressed
toward “REMOTE”.
3). Ensure that the remote contacts are off.
4). Use 20 ~ 24 #AWG wire to connect the remote control terminals.
5). Remote control ON/OFF inverter setup status:
GND
TR
OFF : INV. OFF
ON : INV. ON
ENB
BAT+
BAT-
+
-
DC
POWER
GND
ENB
OFF : INV. OFF
ON : INV. ON
ENB
OFF : INV. OFF
ON : INV. ON
LOW : INV. OFF (TR OFF)
HI : INV. ON (TR ON)
GND
ENB
NOTE: At one time, only one remote function should used to control the inverter.
The maximum voltage value is 60VDC.
▌
Dry Contact Terminals:
Dry contact terminals may be connected to a Form C relay for “FAULT”
indication. When “FAULT” occurs, the relay switches.
NOTE: Fault conditions include Input under/over voltage, Output Short Circuit,
Over Temperature, Over-load and, Fan Failure.
Specifications of the Relay
Maximum
Voltage Load
Contact Rating Number of
operations
Operating/Storage
Temperature
N.O.
N.C.
240 VAC Resistive
16 A
100,000
-30℃~70℃
240 VAC Resistive
8 A
30 VDC Resistive
16 A
30 VDC Resistive
8 A
▌
Remote Control Terminal: