Page 23: Model, 60 vdc max, 36 vdc ~ 44 vdc, Sr series inverter
SR Series Inverter
22
Menu
Status
Buzzer
Message
Power ON or Push Keypad
ON
Alert
FAN Fail or UV Alarm or Overload Alarm ON
Shutdown
OVP or UVP or OLP or OTP
ON
Disable
Any
OFF
4).
Alert Setup: When alert occurs, the internal Dry Contact Relay will
open / close. (See details in Section 3-1-6)
Default= Alert, SHDN
Setting Range= Disable / Shutdown / Alert / Alert, SHDN
Menu
Status
Relay
Alert
FAN Fail or UV Alarm or Overload Alarm
ON
Shutdown
OVP or UVP or OLP or OTP
ON
Disable
Any
OFF
5-3-2.
I/P Parameter (Select Menu):
6).
OVP Setting: Sets the Over Voltage Protection (OVP) and shutdown.
Default= 34 VDC for 24 V Model, 60 VDC for 48 V Model
Model
Setting Value Range
24 V
30 VDC ~ 34 VDC
48 V
60 VDC MAX.
7).
OVP Recovery: When the DC input voltage is higher than the OVP
setting, the inverter shuts-down; Once the input voltage
falls below the set OVP value, the inverter will
automatically restart.
Default= 30 VDC for 24 V Model, 56VDC for 48 V Model
Model
Setting Value Range
24 V
28 VDC ~ 32 VDC
48 V
56 VDC ~ 60 VDC
8).
UVP Setting: Setting the inverter’s Under Voltage Protection (UVP) and
Shutdown.
Default= 18 VDC for 24 V Model, 36 VDC for 48 V Model
Model
Setting Value Range
24 V
18 VDC ~ 22 VDC
48 V
36 VDC ~ 44 VDC
9).
UVP Recovery
:
When the DC input voltage is below the set UVP value
the inverter shuts-down; Once the input voltage rises
above the set UVP value, the inverter will automatically
restart.
Default= 25 VDC for 24 V Model, 50 VDC for 48 V Model