Green, Orange, Ac input off – Samlex America SR1000-148 User Manual
Page 18: Front lcd panel – display & setup, Sr series inverter
SR Series Inverter
17
status LED’s will turn “Green”, The LCD Display will display “Vi, Vo, FQ, Io“.
THE, inverter will start operating normally.
▌
Set the power switch to the “OFF” position. THE, inverter stops and all
the lights that are on will, go off.
4-4. Protections Features
Model
DC Input (VDC)
Over Temperature Protection
Over Voltage
Under
Voltage
Alarm
Under Voltage
INTERIOR
HEAT SINK
Shut-down Restart
Shut-down Restart Shut-
down Restart
Shut-
down Restart
24 V 30.1~34.1 28~32 19~23 18.1~22.1 23~27 65℃ 45℃ 105℃ 75℃
48 V
60.1
56~60 38~46 36.1~44.1 46~54
5. Front LCD Panel – Display & Setup
5-1. LCD Panel Indications
5-1-1. Set the Power Switch to the “ON” position. THE, inverter starts working
normally. The inverter will be operating in normal condition when either
of the following messages are displayed on the LCD screen:
FQ=60.0 Io =8.5
Vi =24.0 Vo=115
LED's
INDICATORS
LCD
DISPLAY
LCD DISPLAY
SELECTION BUTTONS
5-1-2. LED Indications:
▌
AC GRID: Displays AC input status.
AC Input
LED Status
AC input and DC-AC Inverter
Output are Synchronous
Green
AC input ON
Orange
AC input OFF
Off
Note. Synchronous means that the: grid AC input frequency and DC-AC
inverter output frequency or phase are the same (See details in