Ashcroft GC51 - Industrial Rangeable Pressure Transmitter User Manual

Page 25

background image

25

13.2 Setting Items for Linear Display Mode (Re-scaling in arbitrary user

defined units)
Set the filter before setting the linear display mode (Refer to Section
11.1). The following table is the Setting Example 1, Linear Display Mode,
Section 11-3. This applies when re-scaling in arbitrary user defined units.

Setting

LCD

Setting

Setting

No.

Item

Display

Description

Range

Default*

Display

Selection of

non:pressure

non

mode

pressure display

display mode

mode : Lin

Lin:Linear display

mode

Minimum

Min. pressure

Pressure range

0.0

pressure†

corresponding to

0 to 75%F.S.

OFFSET 9

: 10 (psi)

Maximum

Max. pressure

Pressure range

100.0

pressure†

corresponding to

25 to 100%F.S.

FULL SCALE 10

: 60 (psi)

Decimal

Display after

0,1,2,3 digit

0

point

decimal point

position

Number of digits

: 2 (digit)

OFFSET

OFFSET

–1999 to 1999

0

corresponding to

min. pressure 6

: 0.00 (ton)

FULL

FULL SCALE

–1999 to 1999

1000

SCALE

corresponding to

mAX. pressure 7

: 5.00 (ton)

Output

Analog output

Maximum display

0.0

zero point††

zero point (4mA)

span: –10

: 0.0 (%F.S.)

to 110%F.S.

Output

Analog output

Maximum display

100.0

span point††

span point (20mA)

span: –10

: 100.0 (%F.S.)

to 110%F.S.

Loop

Arbitrary change of

Display: linear

0.00

check‡

linear display and

display

(4.0mA)

analog output

Analog output

: 5.00 (ton)

4 to 20mA

n

L;n

d

0.00

d

5.00

d

2

p

60.0

[

5.00

a 100.0

a

0.0

p

10.0

-