Clary SP Series-Model PD User Manual
Page 35

T H E C O N T I N U O U S P O W E R C O M P A N Y
35
 
 
 
 
 
This option is used in the “Standby Mode”. When “ON”, the UPS will force a break in power to the 
cabinet for 2.5 seconds after utility power has returned. This is used when you need a hard restart to 
the controller when coming out of flash. To Change the value, press the arrow buttons. Once at the 
desired value, press the Enter/Show Time button to save. 
 
 
 
 
 
 
This option is used in the “Continuous Operating Mode” when delayed flash is used. When “ON”, the 
UPS will force a break in power to the cabinet for 2.5 seconds after utility power has returned if flash 
trigger in minutes or volts occurs. This is used when you need a hard restart to the controller when 
coming out of flash. To Change the value, press the arrow buttons. Once at the desired value, press 
the Enter/Show Time button to save. 
 
 
 
 
 
This enables the flash trigger in minutes option. The Timer NO/NC contacts on the UPS will activate off 
the Timer. To Change the value, press the arrow buttons. Once at the desired value, press the 
Enter/Show Time button to save. 
 
 
 
 
 
 
This enables the Timer NO/NC contacts on the UPS to activate whenever utility power is lost. 
 
By changing the Flash Status Pin value, the Utility Status Pin value will change to the opposite value. 
To Change the value, press the arrow button. Once at the desired value, press the Enter/Show Time 
button to save. 
 
LONG RETURN ALWAYS 
current value = OFF 
LONG RETURN FLASH 
current value = OFF 
FLASH STATUS PIN 
current value = OFF 
UTILITY STATUS PIN 
current value = ON 