T H E C O N T I N U O U S P O W E R C O M P A N Y

34






This is the battery voltage that specifies the trip point that activates the Low Battery NO/NC contacts on
the UPS. Used for delayed flash. To Change the value, press the arrow buttons. Once at the desired
value, press the Enter/Show Time button to save. The screen will now show the new value. Default is
69.






This will set the Battery Test Interval. The unit will perform a battery self test to determine the condition
of the battery. To Change the value, press the arrow buttons. Once at the desired value, press the
Enter/Show Time button to save. The screen will now show the new value. Default is 160.






This calibration parameter sets the low point at which the UPS switches over to UPS Power. Used
when unit is set in the standby mode. Flash contacts will activate. It is Not recommended to change
this parameter unless instructed to do so by the factory.






This calibration parameter sets the high point at which the UPS switches over to UPS Power. Used
when unit is set in the standby mode. Flash contacts will activate. It is Not recommended to change
this parameter unless instructed to do so by the factory.






This screen will allow you to operate the unit “ONLINE” (Continuous Operating Mode) or “OFFLINE”
(Standby Mode). To Change the value, press the arrow buttons. Once at the desired value, press the
Enter/Show Time button to save. Be sure your load is not over the max rating of the unit before
turning the UPS ONLINE.

FLASH TRIGGER (VOLT)
current value = 69

BATTERY TEST (HOURS)
current value = 160

CALIB PARAMETER #9
current value = 0

CALIB PARAMETER #10
current value = 0

TRAFFIC ONLINE OPER
current value = ON