Clear user adjustment of co2 measurement, Adjust humidity measurement, Show current rh adjustment – Vaisala GMW90 User Manual
Page 57: Clear user adjustment of co, Measurement

Chapter 4 _________________________________________________________________ Operation
VAISALA ________________________________________________________________________ 55
Clear User Adjustment of CO
2
Measurement
CCO2 [RESET]
Example:
>pass 9000
>cco2 reset
OK
Adjust Humidity Measurement
Use the CRH command to perform a humidity adjustment of the relative
humidity (RH) measurement. You can do a 1-point or a 2-point
adjustment, or clear the adjustment information from the HTM10
module. Note that the factory adjustment will remain intact when user
adjustment is cleared.
NOTE
Before using the CRH command, read section Notes for RH Adjustment
Show Current RH Adjustment
CRH
Example (showing default offset and gain):
>pass 9000
>crh
RH Gain : 1.000
RH Offset : 0.000