“Normal Operation All Day” - “Economy Mode All Day” and “Normal

Operation Between.” Only one Operating Mode can be active, the

factory default is Normal Operation All Day.

Normal operation All day: When this operating mode is active the

normal Operating Set Point is used for the entire day.

Economy Mode All day: When this operating mode is active the

Economy Set Point is used for the entire day.

Normal operation Between: When this operating mode is active

there will also be start and stop times to program. The normal

Operating Set Point is used between the programmed start and stop

times and the Economy Set Point will be in effect during the rest of

the day. There is one start time and one stop time event per day.

EConoMy ModE sEttInGs

setpoint Adjustment Value

ACtIon

dIsPLAy

From the Desktop Screen, press the Operational Button underneath “MENU”

to enter the Main Menu.
Notice how the text above the Operational Buttons on the display changes

as you navigate through the various menus and screens.

Use the Up/Down buttons to select (highlight in black) the Economy Mode

Setup menu from the Main Menu. Press the Operational Button underneath

“SELECT” to enter the Economy Mode Setup menu.

Use the Up/Down buttons to select (highlight in black) Setpoint Adjustment.

Press the Operational Button underneath “CHANGE” to activate the

adjustment mode for the Setpoint Adjustment value.

Use the Up/Down buttons to change the Setpoint Adjustment to the desired

value. The Setpoint Adjustment value is adjustable from 2°F to 50°F. The

factory default is 20°F.

Notice how the text above the Operational Buttons on the display changes

to “UPDATE” & “CANCEL” when the adjustment mode is activated and how

the current value is outlined rather than highlighted in black.

Press the Operational Button underneath “UPDATE” to enter and confirm

the new value. Pressing the Operational Button underneath “CANCEL”

would discard the new value and retain the previous value.

The new Setpoint Adjustment value should now be displayed as the

current value.