beautypg.com

State CSB 120 54 IFE User Manual

Page 25

background image

25

hEAtEr stAtus MEnu

This menu displays non adjustable operational information. This

menu contains more information that can be displayed on one screen

of the LCD display. Use the Up & Down Buttons to navigate to the

bottom of this menu.

top of Menu

Bottom of Menu

status
Displays the current Operating State of the control system. IE:

Heating, Standby, Fault see Table 8.

Element Banks on
Displays the current number of heating element Banks the control

system has energized. Each Bank of elements contains 3 heating

elements.

ECo Contact
Displays the current state of the ECO high temperature limit

switch contacts. The ECO switch is located inside the immersion

Temperature Probe (two red wires).

Enable / disable 1 & 2
Displays the current state, open or closed, of the two Enable/Disable

circuits (J7 socket on the CCB - see wiring diagrams) provided

for external supervisory controls such as building EMS (Energy

Management System). Both of these Enable/Disable circuits must be

closed to “enable” heating operation. If either Enable/Disable circuit is

open for any reason heating operation will be “disabled.” There is a plug

with two jumper wires installed from the factory in the CCB J7 socket to

enable heating operation when external controls are not in use.

Service Note: If a supervisory control(s) is used to enable/disable

heating operation, install field wiring between the J7 socket on the CCB

and a set of “dry contacts” on the external control per all applicable

building codes. This is a switching circuit only: DO NOT apply any

external voltage or connect any load (IE: relay coil) to either circuit.

Element Bank on
Displays the on/off status of each Bank of heating elements. Yes =

On, No = Off.

Alarm Condition
Displays the status of the user definable Alarm Output function - see

Alarm Output Setup Menu. Yes = alarm condition has been met, No

= alarm condition has not been met.
Alarm relay output
Displays the state of the normally open contacts of the Alarm Output

relay. This relay (J3 contacts on the CCB) is used for building EMS

(Energy Management System) notification of operational conditions

such as Fault conditions.

EConoMy ModE sEtuP MEnu

This menu contains settings used to establish an “Economy Set

Point” and “Economy Mode” operating periods. This control system

feature can help reduce operating costs during unoccupied, low load,

or peak demand periods.

desktop screen during Economy Mode

Economy Mode setup Menu

setpoint Adjustment
Adjustable user setting (2°F to 50°F - factory default is 20°F) the

control system uses to calculate the “Economy Set Point.” The Economy

Set Point = normal Operating Set Point minus the programmed Setpoint

Adjustment value. The Economy Set Point is the water temperature

the control system maintains during programmed Economy Mode time

periods. “Economy Set Point” is displayed instead of “Operating Set

Point” and “Economy Mode” appears beneath the current time on the

Desktop Screen during Economy Mode time periods.
Current time
Seven Day 24 hr clock. Use this menu item to set the current time

and day of the week. Current day and time are not set from the

factory. “Clock Not Set” will be displayed on the Desktop until the

time/day has been initially set.

heater In Economy Mode
Displays whether the control system is currently operating in

Economy Mode or not.

daily operating Mode (sun - Mon - tue - wed - thu - fri - sat)
Seven daily sub menus are listed at the bottom of the Economy Mode

Setup menu. There are 3 Operating Modes in each sub menu;