ConVErsIon to sInGLE PhAsE
When the heater is shipped for connection to a three-phase electrical
service, it may be connected to a single-phase electrical service of
the same voltage by:
1. Disconnect blue wires from terminal L2.
2. Connect all blue wires to terminal L1 (with black wires).
3. Disconnect all red wires from terminal L3.
4. Connect all red wires to terminal L2 (with yellow wires).
5. Connect incoming power to terminals L1 and L2.
ConVErsIon to thrEE PhAsE
When heater is shipped for connection to a single-phase electrical
service, it may be connected to a three-phase electrical service of
the same voltage by:
1. Disconnect blue wires from terminal L1
2. Disconnect red wires from terminal L2.
3. Connect all blue wires to terminal L2 (with yellow wires).
4. Connect red wires to terminal L3.
5. Connect incoming power to terminals L1, L2 and L3.
nInE ELEMEnts - sInGLE And thrEE PhAsE
dIAGrAM 4.
- CSB 120 45 IFE CSB 120 405 IFE CSB 120 36 IFE CSB 120 30 IFE CSB 120 27 IFE CSB 120 24 IFE CSB 120 18 IFE CSB 120 15 IFE CSB 120 135 IFE CSB 120 12 IFE CSB 120 9 IFE CSB 120 6 IFE CSB 82 54 IFE CSB 82 45 IFE CSB 82 405 IFE CSB 82 36 IFE CSB 82 30 IFE CSB 82 27 IFE CSB 82 24 IFE CSB 82 18 IFE CSB 82 15 IFE CSB 82 135 IFE CSB 82 12 IFE CSB 82 9 IFE CSB 82 6 IFE CSB 52 54 IFE CSB 52 45 IFE CSB 52 405 IFE CSB 52 36 IFE CSB 52 30 IFE CSB 52 27 IFE CSB 52 24 IFE CSB 52 18 IFE CSB 52 15 IFE CSB 52 135 IFE CSB 52 12 IFE CSB 52 9 IFE CSB 52 6 IFE