differential settings
Adjustable user setting(s) 1°F to 20° range; factory default is 2°F.

The water heaters covered in this Instruction Manual will have 3, 6 or

9 heating elements. Each group of 3 heating elements is one “Bank” of

heating elements. Heating elements are energized in Banks of 3. Each

Bank of heating elements will have a Differential Setting associated

with it. Differential Settings are located in the Temperatures Menu.
There is a 1st Differential Setting on all models. There will be one

additional Differential Setting visible/adjustable for each additional

Bank of (3) heating elements.

operating sequence
With an Operating Set Point of 120°F and all Differential settings at 2°F

the On/Off sequencing of heating element Banks would be as follows:

BANK NUMBER

DIFFERENTIAL

SETTING

TURN ON

TEMP

TURN OFF

TEMP

Bank 1

2°F

118°F

120°F

Bank 2

2°F

116°F

118°F

Bank 3

2°F

114°F

116°F

tank temperature
Non adjustable information display. Current water temperature as sensed

by the control system from the immersion Temperature Probe.

tank Probe offset
User adjustable setting -5°F to +5°F range; factory default is 0°F. If the

current Tank Temperature is sensed (from the immersion Temperature

Probe) at 120°F and the offset is adjusted to -5°F the control system

would calibrate or “offset” the Tank Temperature to 115°F. Heating cycles

would then start/stop based on the calibrated Tank Temperature.

Used to calibrate for slight differences in control system temperature

sensing. This can improve the precision of temperature control in

the storage tank and at points of use. This feature can also be

used to compensate for building recirculation loops (hot water

returning to the storage tank) that may cause the heating cycle to

terminate prematurely.

tEMPErAturE sEttInGs

The Operating Set Point and the Differential Settings are adjusted

in the Temperatures Menu. The following instructions explain how to

adjust these user settings and navigate the control system menus.

ACtIon

dIsPLAy

From the Desktop Screen, press the Operational Button underneath “MENU”

to enter the Main Menu.
Notice how the text above the Operational Buttons on the display changes

as you navigate through the various menus and screens.

With Temperatures selected (highlight in black) in the Main Menu, press

the Operational Button underneath “SELECT” to enter the Temperatures

Menu.
If Temperatures is not selected use the Up and Down buttons to select this

menu item.

With the Operating Set Point selected in the Temperatures Menu, press

the Operational Button underneath “CHANGE” to activate the adjustment

mode for this menu item.

Press the Up and Down buttons to adjust the Operating Set Point to the

desired setting.
Press the Operational Button underneath “UPDATE” to confirm the new

setting. Press the Operational Button underneath “CANCEL” to discard the

new setting and retain the previous setting.
The new Operating Set Point value should now be displayed as the current

value.

NOTE: Use this same procedure to adjust the Differential settings and the

Tank Probe Offset in the Temperatures Menu.
This same procedure is used to change user settings in other control system

menus.