beautypg.com

State CSB 120 54 IFE User Manual

Page 11

background image

11

by the manufacturer. The valve is certified by a nationally

recognized testing laboratory that maintains periodic inspection

of production of listed equipment of materials as meeting the

requirements for Relief Valves for Hot Water Supply Systems,

ANSI Z21.22 • CSA 4.4, and the code requirements of ASME.

If replaced, the new valve must meet the requirements of local

codes, but not less than a combination temperature and pressure

relief valve rated/sized and certified as indicated in the above

paragraph. The new valve must be marked with a maximum set

pressure not to exceed the marked hydrostatic working pressure

of the water heater (150 psi = 1,035 kPa) and a discharge

capacity not less than the water heater Btu/hr or KW input rate

as shown on the water heater’s model rating plate.

For safe operation of the water heater, the temperature and

pressure relief valve must not be removed from its designated

opening nor plugged. The temperature-pressure relief valve

must be installed directly into the fitting of the water heater

designed for the relief valve. Install discharge piping so that

any discharge will exit only within 6 inches (15.2 cm) above, or

external to the structure. Do not pipe the discharge to a crawl

space. Be certain that no contact is made with any live electrical

part. The discharge opening must not be blocked or reduced in

size under any circumstances. Excessive length, over 30 feet

(9.14 m), or use of more than four elbows can cause restriction

and reduce the discharge capacity of the valve.

No valve or other obstruction is to be placed between the relief valve

and the tank. Do not connect discharge piping directly to the drain

unless a 6” (15.2 cm) air gap is provided. To prevent bodily injury,

hazard to life, or property damage, the relief valve must be allowed

to discharge water in adequate quantities should circumstances

demand. If the discharge pipe is not connected to a drain or other

suitable means, the water flow may cause property damage.

The Discharge Pipe:

• Shall not be smaller in size than the outlet pipe size of the

valve, or have any reducing couplings or other restrictions.

• Shall not be plugged or blocked.
• Shall not be exposed to freezing temperatures.
• Shall be of material listed for hot water distribution.
• Shall be installed so as to allow complete drainage of both

the Temperature-Pressure Relief Valve and the discharge

pipe.

• Must terminate a maximum of six inches above a floor drain

or external to the building. In cold climates, it is recommended

that the discharge pipe be terminated at an adequate drain

inside the building.

• Shall not have any valve or other obstruction between the

relief valve and the drain.

The temperature-pressure relief valve must be manually

operated at least once a year. Caution should be taken to

ensure that (1) no one is in front of or around the outlet of the

temperature-pressure relief valve discharge line, and (2) the

water manually discharged will not cause any bodily injury or

property damage because the water may be extremely hot. If

after manually operating the valve, it fails to completely reset

and continues to release water, immediately close the cold water

inlet to the water heater, follow the draining instructions in this

manual, and replace the temperature-pressure relief valve with

a properly rated/sized new one.

If you do not understand these instructions or have any questions

regarding the temperature-pressure relief valve call the toll free

number listed on the back cover of this manual for technical

assistance.

wAtEr LInE ConnECtIons

This manual provides detailed piping installation diagrams (see

back section of this manual) for typical methods of application.

For the heater inlet and outlet connections, dielectric unions are

recommended. The water heater may be installed by itself, or with a

separate storage tank, on both single and two-temperature systems.

When used with a separate storage tank, the circulation may be either

by gravity or by means of a circulating pump. When a circulating

pump is used it is important to note that the flow rate should be

slow so that there will be a minimum of turbulence inside the heater.

CLosEd wAtEr systEMs

Water supply systems may, because of code requirements or

such conditions as high line pressure, among others, have

installed devices such as pressure reducing valves, check valves,

and back flow preventers. Devices such as these cause the water

system to be a closed system.

thErMAL EXPAnsIon

As water is heated, it expands (thermal expansion). In a closed

system the volume of water will grow when it is heated. As the volume

of water grows there will be a corresponding increase in water pressure

due to thermal expansion. Thermal expansion can cause premature

tank failure (leakage). This type of failure is not covered under the limited

warranty. Thermal expansion can also cause intermittent temperature-

pressure relief valve operation: water discharged from the valve due to

excessive pressure build up. This condition is not covered under the

limited warranty. The temperature-pressure relief valve is not intended

for the constant relief of thermal expansion.
A properly sized thermal expansion tank must be installed on

all closed systems to control the harmful effects of thermal

expansion. Contact a local plumbing service agency to have a

thermal expansion tank installed.