Maintenance, Recommended wire sizes by length – Outback Power Systems FX Series Installation Manual User Manual
Page 53
51
FX Model
Typical DC
AMPS
NEC AMPS
1-3’ one way
3-5’ one way
5-10’ one way
FX 2012T
167
208
4/0
4/0
4/0
FX2524T
GTFX252
104
104
130
130
2/0
2/0
2/0
FX3048T
GTFX3048
63
78
1/0
1/0
1/0
VFX2812
233
292
4/0
4/0
300 MCM
VFX3524
GVFX3524
146
182
4/0
4/0
4/0
VFX3648
GVFX3648
75
94
1/0
1/0
1/0
MAINTENANCE
If damaged or malfunctioning, the FX should be repaired by a qualifi ed user, installer, or service center
following OutBack Power Systems’ instructions and guidelines. Please contact your energy dealer for
assistance. Incorrect repairs and/or reassembly risks malfunction, electric shock or fi re.
For routine, user-approved maintenance:
• Disconnect all circuit breakers and related electrical connections before doing any cleaning or
adjustments.
• Solar modules may produce hazardous voltages when exposed to light; cover them with opaque
material before servicing any connected equipment or service at night.
• If a remote or automatic generator start system is used, disable the automatic starting circuit and/or
disconnect the generator from its starting battery while servicing. This will prevent accidental it to
starting or operation.
Recommended Wire Sizes by Length