beautypg.com

Maintenance, Recommended wire sizes by length – Outback Power Systems FX Series Installation Manual User Manual

Page 53

background image

51

FX Model

Typical DC

AMPS

NEC AMPS

1-3’ one way

3-5’ one way

5-10’ one way

FX 2012T

167

208

4/0

4/0

4/0

FX2524T

GTFX252

104

104

130

130

2/0

2/0

2/0

FX3048T

GTFX3048

63

78

1/0

1/0

1/0

VFX2812

233

292

4/0

4/0

300 MCM

VFX3524

GVFX3524

146

182

4/0

4/0

4/0

VFX3648

GVFX3648

75

94

1/0

1/0

1/0

MAINTENANCE

If damaged or malfunctioning, the FX should be repaired by a qualifi ed user, installer, or service center

following OutBack Power Systems’ instructions and guidelines. Please contact your energy dealer for

assistance. Incorrect repairs and/or reassembly risks malfunction, electric shock or fi re.

For routine, user-approved maintenance:

• Disconnect all circuit breakers and related electrical connections before doing any cleaning or

adjustments.

• Solar modules may produce hazardous voltages when exposed to light; cover them with opaque

material before servicing any connected equipment or service at night.

• If a remote or automatic generator start system is used, disable the automatic starting circuit and/or

disconnect the generator from its starting battery while servicing. This will prevent accidental it to

starting or operation.

Recommended Wire Sizes by Length