AC WIRING NOTES FOR THE NON-MOBILE FX

AC HOT OUT

• AC hot output conductor (black) wire

gauge must be sized to the breakers and
loads.

AC NEUTRAL OUT/AC NEUTRAL IN

• Both neutral terminals are common with

each other within the FX.

• Only one neutral needs to connect at the

terminal if a separate common neutral bus
bar is installed.

CHASSIS GROUND

• Both CHASSIS GROUND terminals are

common within the FX.

• The AC input and AC output ground wires

can connect to these terminals or one can
be connected if a common ground bus
bar is installed.

AC HOT IN

• The AC hot input conductor (black) must

be supplied through a 60 amp maximum
AC branch rated circuit breaker.

• 6 AWG (.184” or 4.11 mm) wire is

recommended for the FX’s AC transfer
relay.