beautypg.com

Outback Power Systems FX Series Installation Manual User Manual

Page 48

background image

46

NOTE:

This is the maximum continuous DC current that the FX will draw from the batteries when inverting.

FX2012MT

190ADC (ADC = Amps DC)

FX2524MT 95ADC

FX2532MT 90ADC

FX3048T 60ADC

VFX2812M 265ADC

VFX3524M 170ADC

VFX3232M 115ADC

VFX3648 85ADC

AC INPUT OPERATING VOLTAGE RANGE

NOTE:

This is the recommended AC input voltage range to be supplied to the FX. Voltages outside of

this range may damage AC loads connected to the FXs AC output terminals.

All FX Series Inverter/Chargers

90 – 150VAC (VAC = volts AC)

MAXIMUM AC INPUT CURRENT

An AC input source connected to the FX supplies power for two separate internal AC circuits – the AC

transfer switch and the battery charging system. The AC transfer switch transfers the AC input power

to the AC loads. The FX’s battery charger will “back off ” if the total AC loads—including the charger—

exceed the AC input current limit (default setting is 28AAC). This “Input Limit” can be adjusted using

the MATE to avoid overloading a generator or trip a circuit breaker. If your generator cannot produce

28AAC or you are connecting to an AC input source that has a breaker that is rated for less than

30AAC, please refer to the FX and VFX Series Inverter/Charger Programming Manual to change this

setting.

All “Mobile” FXs

30AAC per FX (AAC = Amps AC)

All 120VAC FXs

60AAC per FX (AAC = Amps AC)

MAXIMUM CURRENT FOR BATTERY CHARGER

Due to heat restraints, the FX limits incoming AC current to recharge the battery. Please refer to the FX

and VFX Series Inverter/Charger Programming Manual to adjust this setting. The battery charger has

an effi

ciency of better than 80%. Other factors, such as cable losses, might reduce this effi

ciency.

RATED DC INPUT CURRENT