Outback Power Systems FX Series Installation Manual User Manual
Page 51
49
12 VDC System
DEFAULT
MINIMUM
MAXIMUM
Float Voltage
13.6V
12V
15V
Absorb Voltage
14.4V
13V
16V
EQ Voltage
14.4V (24VDC Grit-Tie=29.2) 14V
17V
ReFloat
12.5V
11V
13V
LBCO
10.5V
9V
12V
LBCI
12.5V
10V
14V
Sell RE
13V
10V
15V
Gen Alert
Off Set Point
14V
12V
18V
On Set Point
11V
10V
14V
Load Shed Off Set Point
11V
10V
14V
Vent Fan ON Set Point
13V
10V
16V
Diversion ON Set Point
14.6V
12V
16V
Absorb Time
1.0 hours
0.0 hours
24.0 hours
EQ Time
1.0 hours
0.0 hours
24.0 hours
Float Time
1.0 hours
0.0 hours
24.0 hours
AC2/Gen Transfer Delay
(Cycles for AC)
60 cycles*
(*20 for Grid-Tie)
0 cycles
240 cycles
Search
6
0
50
Grid Lower Limit
108V
40V
115V
Grid Upper Limit
140
80V
220V
Grid Upper Limit
140V
130V
150V
Grid Connect Delay
.5 min
.2 min
15.0 min
DROP or USE
USE
N/A
N/A
Charger OFF/AUTO/ON
AUTO
AUX Output Option
COOL FAN
Gen Alert ON Delay
4 min
0 min
240 min
Gen Alert OFF Delay
9 min
0 min
240 min
Vent Fan OFF Delay
5 min
0 min
30 min
Gen Window Lower Limit
108V
40V
115V
Gen Upper Window Limit
140V
130V
150V
AC1/Grid Transfer Delay
6 Cycles of AC
0 Cycles of AC
240 Cycles of AC
Set AUX Control
AUTO
Search Pulses
8
2
20
Search Pulse Spacing
60 Cycles Ac
4 Cycles AC
120 Cycles AC
Stacking Phase
1 or 2 phase
InPut Select
Master Gen
Charge Rates
Vented 24 & 48 VDC
18 AAC
0 AAC
20 AAC
Vented 12 VDC
12 AAC
0 AAC
14 AAC
Sealed 24 & 48 VDC
10 AAC
0 AAC
14 AAC
Sealed 12 VDC
10 AAC
0 AAC
12 AAC
Grid Input Settings
Set AC Input Size
Mobile
28 Amp
5 Amp
30 Amp
Non-Mobile U.S.
48 Amp
5
Grid-Tie
50 Amp
Gen Input Settings
Mobile
28 Amp
2Amp
30 Amp
Non-Mobile U.S.
48 Amp
2 Amp
60 Amp
Grid-Tie
50 Amp
Set VAC
120V (230V Export)
110V GT (210V Export,
105V Off -Grid and Mobile)
125V (240V Export)
FX Default Values (subject to change with FX upgrades)
C
o
rr
ec
tion F
a
c
tor •24VDC: Multiply 12VDC values by 2 •32VDC: Multiply 12VDC values by 2.64 •48VDC: Multiply 12VDC values b
y 4