3-PHASE FX SYSTEM

• This system produces 120VAC per phase and 208VAC from phase to phase. There can only be one FX per phase

on a 3-phase system.

• The non-Mobile AC wiring from the AC source and to the AC loads must handle 60 amps AC.

• All other non-Mobile AC wiring must handle a capacity of 60 amps AC; Mobile must handle 30 amps AC.

• This system can power continuously up to 10.8kW of loads depending on which model is used.

• Connecting more power than the continuous rating of the FX may cause breakers to trip or the FX to shut off its

AC output.

• The jumper in the HUB must be moved for 3-phase confi guration (please see the HUB Installation and User

Guide).

NOTE:

Program the bottom FX as Master (3ph MASTER) and the two lower FXs as 3-phase Slaves

(3ph SLAVE). Keep the phases in order: phase one is connected to the FX programmed L1; phase
two is connected to L2; and phase three to L3 (or phases A, B, and C to inverters A, B, and C).

GT

Grid-Tie FXs cannot be used with this configuration

.