42
Nominal DC Input Voltage Range
12VDC
Nominal AC Voltage / Frequency
120VAC / 60 HZ
Continuous Power Rating at 25C Ambient
2800VA
Continuous AC RMS Output at 25°C
23.3 Amps AC
Idle Power - Full AC Output
≈ 20 Watts DC
Idle Power - Search Mode
2.6 Watts DC
Typical Effi
ciency
90%
Total Harmonic Distortion - Typical
2%
Output Voltage Regulation
± 2%
Maximum Output Current – Peak (1 mSec)
56 amps AC
Maximum Output Current - RMS (100 mSec)
40 amps AC
AC Overload Capability - Surge
4800VA
AC Overload Capability - 5 Second
4000VA
AC Overload Capability - 30 Minutes
3200VA
AC Input Current Maximum
30 Amps AC
AC Input Voltage Range
80 to 150VAC
AC Input Frequency Range
54.0 to 66.0 Hz
DC Input Range
10.5 to 17.0 VDC
DC Input Current – Rated Power
280 Amps DC
Continuous Battery Charger Output
125 Amps DC
VFX2812M
VFX3232M
Nominal DC Input Voltage Range
32VDC
Nominal AC Voltage / Frequency
120VAC / 60 HZ
Continuous Power Rating at 25C Ambient
3200VA
Continuous AC RMS Output at 25°C
26.6 Amps AC
Idle Power - Full AC Output
≈ 21 Watts DC
Idle Power - Search Mode
2.6 Watts DC
Typical Effi
ciency
92%
Total Harmonic Distortion - Typical
2%
Output Voltage Regulation
± 2%
Maximum Output Current – Peak (1 mSec)
56 amps AC
Maximum Output Current - RMS (100 mSec)
40 amps AC
AC Overload Capability - Surge
4800VA
AC Overload Capability - 5 Second
4000VA
AC Overload Capability - 30 Minutes
4000VA
AC Input Current Maximum
30 Amps AC
AC Input Voltage Range
80 to 150VAC
AC Input Frequency Range
54.0 to 66.0 Hz
DC Input Range
28.0 to 45.3 VDC
DC Input Current – Rated Power
120 Amps DC
Continuous Battery Charger Output
45 Amps DC