beautypg.com

Ac and dc grounding requirements – Outback Power Systems FX Series Installation Manual User Manual

Page 10

background image

8

AC AND DC GROUNDING REQUIREMENTS

• Connect only to a grounded, permanent wiring system. Ensure there is only one neutral-ground

connection in the system at any time. Some codes require this connection be made at the main

panel only.

• Some generators have their own neutral ground connection. If a generator is used, its neutral-

ground connection will need to be disengaged for proper system operation.

• For all installations, the negative battery conductor should be bonded to the grounding system at

one (and only one) point in the system.

• OutBack products are not designed for use in a positive grounded system. Please contact OutBack

Technical Support for further information.

The equipment ground on each is marked with this symbol:

Box lug for grounding the FX chassis