FX2012MT

AC Max = 12AAC (Default = 10AAC)

DC Max = 100ADC

FX2524MT

AC Max = 14AAC (Default = 12AAC)

DC Max = 55ADC

FX2532MT

AC Max = 14AAC (Default = 12AAC)

DC Max = 40ADC

FX3048T

AC Max = 14AAC (Default = 12AAC)

DC Max = 35ADC

VFX2812M

AC Max = 16AAC (Default = 14AAC)

DC Max = 125ADC

VFX3524M

AC Max = 20AAC (Default = 18AAC)

DC Max = 85ADC

VFX3232M

AC Max = 20AAC (Default = 18AAC)

DC Max = 60ADC

VFX3648

AC Max = 20AAC (Default = 18AAC)

DC Max = 45ADC

AC INPUT FREQUENCY RANGE

NOTE: If the AC input source is out of the range noted below, the FX will not connect or stay connected.

All FX Models

56 - 64 Hz

MAXIMUM AC OUTPUT CURRENT

This is the amount of surge current that the FX will quickly supply for a split second. Depending on the
size of the surge, the FX can be overloaded for a minimum time of 5 seconds to a maximum time of 30
minutes.

All 12 VDC FXs

56AAC per FX for 1 millisecond

All Other FXs

70AAC per FX for 1 millisecond

MAXIMUM CONTINUOUS OUTPUT POWER

An FX Series Inverter/Charger’s model number indicates its maximum continuous output power by
changing the last two digits to zeros. For instance, an FX2012MT has a maximum continuous output

power of 2000VA (volt-amps).

FX2012MT

2000VA (VA = volt-Amps)

FX2024MT 2000VA

FX2532MT 2500VA

FX2548T 2500VA

VFX2812M 2800VA

VFX3524M 3500VA

VFX3232M 3200VA

VFX3648 3600VA

MAXIMUM AND DEFAULT AC INPUT AND DC (bulk stage) OUTPUT VALUES