Ac hot out, Ac neutral out/ac neutral in, Chassis ground – Outback Power Systems FX Series Installation Manual User Manual
Page 23: Ac hot in
21
AC HOT OUT
AC NEUTRAL OUT
CHASSIS GROUND
NEU/GROUND BOND
AC NEUTRAL IN
AC HOT IN
FULL
OK
LOW
INVERTER
AC IN
BATTERY TEMP
MATE/HUB
INVERTER ON/OFF
INVERTER
ON/OFF
AUX+
AUX-
XCT-
XCT+
R E M O V E J U M P E R
T O D I S A B L E
G R O U N D S W I T C H I N G
BATTERY
STATUS
INVERTER
STATUS
ERROR
AC HOT OUT
• Supplies the AC hot output conductors
through a 30 amp maximum AC branch
rated circuit breaker using 10 AWG (.102” or
2.59 mm) wire and connect to the AC
AC NEUTRAL OUT/AC NEUTRAL IN
• Connects the AC neutral input conductor to
the AC NEUTRAL IN terminal.
• Connects the AC neutral output conductor
to the AC NEUTRAL OUT terminal.
• These terminals are common in the Mobile
FX only when an AC source is applied.
• The NEUTRAL IN and NEUTRAL OUT
conductors should not be common
(connected in any way) prior to connection
with a Mobile FX
CHASSIS GROUND
• Connects both the AC input and AC output
ground conductors to the CHASSIS GROUND
and NEU/GROUND BOND terminals.
• If there is only one Mobile FX in the system,
leave the copper bus (provided) installed
between the CHASSIS GROUND and NEU/
GROUND BOND terminals. If there is more
than one Mobile FX in the system, remove
the copper bus from every Slave FX.
AC HOT IN
• The AC hot input conductor (black) must be
supplied through a 30 amp maximum AC
branch rated circuit breaker and connected
to the AC HOT IN.
• 10 AWG (.102” or 2.59 mm) wire is required
for the FX’s AC transfer switch.
AC WIRING NOTES FOR THE MOBILE FX
M