Ac hot out, Ac neutral out/ac neutral in, Chassis ground – Outback Power Systems FX Series Installation Manual User Manual

Page 23: Ac hot in

background image

21

AC HOT OUT

AC NEUTRAL OUT

CHASSIS GROUND

NEU/GROUND BOND

AC NEUTRAL IN

AC HOT IN

FULL

OK

LOW

INVERTER

AC IN

BATTERY TEMP

MATE/HUB

INVERTER ON/OFF

INVERTER

ON/OFF

AUX+

AUX-

XCT-

XCT+

R E M O V E J U M P E R
T O D I S A B L E
G R O U N D S W I T C H I N G

BATTERY

STATUS

INVERTER

STATUS

ERROR

AC HOT OUT

• Supplies the AC hot output conductors

through a 30 amp maximum AC branch
rated circuit breaker using 10 AWG (.102” or
2.59 mm) wire and connect to the AC

AC NEUTRAL OUT/AC NEUTRAL IN

• Connects the AC neutral input conductor to

the AC NEUTRAL IN terminal.

• Connects the AC neutral output conductor

to the AC NEUTRAL OUT terminal.

• These terminals are common in the Mobile

FX only when an AC source is applied.

• The NEUTRAL IN and NEUTRAL OUT

conductors should not be common
(connected in any way) prior to connection
with a Mobile FX

CHASSIS GROUND

• Connects both the AC input and AC output

ground conductors to the CHASSIS GROUND
and NEU/GROUND BOND terminals.

• If there is only one Mobile FX in the system,

leave the copper bus (provided) installed
between the CHASSIS GROUND and NEU/
GROUND BOND terminals. If there is more
than one Mobile FX in the system, remove
the copper bus from every Slave FX.

AC HOT IN

• The AC hot input conductor (black) must be

supplied through a 30 amp maximum AC
branch rated circuit breaker and connected
to the AC HOT IN.

• 10 AWG (.102” or 2.59 mm) wire is required

for the FX’s AC transfer switch.

AC WIRING NOTES FOR THE MOBILE FX