Maximum overcurrent protection ampacity – Outback Power Systems FX Series Installation Manual User Manual

Page 50

background image

48

MODEL

AMPACITY

DC BREAKER

DC FUSE

FX2012MT

200 amps

OBDC-250

Class T-400 (Mobile Only)

FX2024MT

175 amps

OBDC-175

Class T-300 (Mobile Only)

FX2532MT

175 amps

OBDC-175

Class T-300 (Mobile Only)

FX2548T 100

amps OBDC-100 Not

Recommended

VFX2812M

200 amps

OBDC-250

Class T-400 (Mobile Only)

VFX3524M

260 amps

OBDC-250

Class T-400 (Mobile Only)

VFX3232M

175 amps

OBDC-175

Class T-300 (Mobile Only)

VFX3648 175

amps OBDC-175 Not

Recommended

GTFX 2524

125 amps

OBDC-175

DO NOT USE

GTFX 3048

75 amps

OBDC-100

DO NOT USE

GVFX 3524

175 amps

OBDC-250

DO NOT USE

GVFX 3648

90 amps

OBDC-125

DO NOT USE

MAXIMUM OVERCURRENT PROTECTION AMPACITY

This rating specifi es the proper overcurrent protection ampacity.

• OBB breakers are panel-mount circuit breakers.

• Class T DC fuses are terminal-mounted and should always be used in conjuncture with a disconnect mechanism.

• FXs used in home installations should use properly sized DC circuit breakers.

• A DC breaker includes both overcurrent protection and disconnect capability.

• OutBack Power Systems recommends Class T fuses for marine installations where a DC disconnect is not required.