Maximum overcurrent protection ampacity – Outback Power Systems FX Series Installation Manual User Manual
Page 50
48
MODEL
AMPACITY
DC BREAKER
DC FUSE
FX2012MT
200 amps
OBDC-250
Class T-400 (Mobile Only)
FX2024MT
175 amps
OBDC-175
Class T-300 (Mobile Only)
FX2532MT
175 amps
OBDC-175
Class T-300 (Mobile Only)
FX2548T 100
amps OBDC-100 Not
Recommended
VFX2812M
200 amps
OBDC-250
Class T-400 (Mobile Only)
VFX3524M
260 amps
OBDC-250
Class T-400 (Mobile Only)
VFX3232M
175 amps
OBDC-175
Class T-300 (Mobile Only)
VFX3648 175
amps OBDC-175 Not
Recommended
GTFX 2524
125 amps
OBDC-175
DO NOT USE
GTFX 3048
75 amps
OBDC-100
DO NOT USE
GVFX 3524
175 amps
OBDC-250
DO NOT USE
GVFX 3648
90 amps
OBDC-125
DO NOT USE
MAXIMUM OVERCURRENT PROTECTION AMPACITY
This rating specifi es the proper overcurrent protection ampacity.
• OBB breakers are panel-mount circuit breakers.
• Class T DC fuses are terminal-mounted and should always be used in conjuncture with a disconnect mechanism.
• FXs used in home installations should use properly sized DC circuit breakers.
• A DC breaker includes both overcurrent protection and disconnect capability.
• OutBack Power Systems recommends Class T fuses for marine installations where a DC disconnect is not required.