Installation Procedures: Route and Attach Overhead Wiring

InfraStruXure Site Planning, Installation, Start-Up

23

For dual-feed devices within a redundant system: attach a power cable from each PDU into

two different Rack PDUs in the NetShelter VX Enclosure.

For single-feed devices within a redundant system with an Automatic Transfer Switch:

connect a power cable to the Automatic Transfer Switch (A and B feeds) and connect the

Automatic Transfer Switch power cord to a Rack PDU in the NetShelter VX Enclosure.

For dual-feed devices in a redundant system with an Automatic Transfer Switch: connect a

power cable from each PDU to the Automatic Transfer Switch’s A and B feeds, and another
power cable from one PDU to a Rack PDU, and the Automatic Transfer Switch’s power cord
to a second Rack PDU in the NetShelter VX Enclosure.

Lay the cables neatly in the Shielding Trough to minimize cable build-up.