8

InfraStruXure Site Planning, Installation, Start-Up

Electrical Requirements and Specifications

Procedures requiring a licensed electrician

Electrical requirements

A licensed electrician must connect utility power. The following procedures

require a licensed electrician:

• connection of utility conductors

• installation of a 200- or 100-amp circuit breaker

• connection to the main input switch

• connection to a branch circuit

See also

To connect utility power, see the utility connection instructions included with your

documentation.

200V Input

415V Input

Service distribution breaker

1,2

200A

100A

Conductors to Main Input switch

1

3W + G

3W + G

Recommended wire sizing

2,3

L1, L2, L3

60mm

2

38mm

2

G

14 mm

2

8 mm

2

1

Provided by customer

2

Consult national and local codes for requirements specific to your installation.

3

CV or CVT cable