INSTALLATION INSTRUCTIONS FOR CMP CABLE CONNECTOR TYPE TMC2
DUBAI
• HOUSTON • NEWCASTLE • SINGAPORE • SHANGHAI • PUSAN • PERTH
DUBAI
• HOUSTON • NEWCASTLE • SINGAPORE • SHANGHAI • PUSAN • PERTH
www.cmp-products.com
www.cmp-products.com
CABLE CONNECTOR COMPONENTS
PLEASE READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION
1. Cable preparation.
Strip back the jacket and armor to suit the equipment geometry.
2. Using the armor measure guide, expose the armor by stripping back the cable jacket by distance “L”.
3. Screw the connector into the equipment, or if it is fitted into a clearance hole, secure with a
locknut.
Loosen the outer nut to ensure that the Grounding Spring (4) and the Jacket Seal (6) are in a
relaxed state. IT IS NOT NECESSARY TO SEPERATE THE CONNECTOR COMPONENTS.
4. Pass the cable through the connector until the armor makes contact with the end stop.
If it is not possible for the conductors to pass through the end stop then it should be removed so
that the armor can make contact with the integral end stop within the entry component.
5. Finally, tighten the Outer Nut (7) to compress the Grounding Spring (4) to secure the armor, and
also to cpmpress the Jacket Seal (6) onto the cable jacket. Do not over-tighten. The Entry
Component (2) and the Outer Nut (7) do not have to close face to face.
THIS COMPLETES THE TERMINATION
2
3
1
1. Face Seal
2. Entry Component
3. End Stop
4. Grounding Spring
5. Angled Spacer
6. Jacket Seal
7. Outer Nut
4
5
6
7
Armor Measure
Guide
L
L
L = Distance from
groove to rear of nut.
End Stop