Notified Body: Sira Certification Service, Rake Lane, Chester CH4 9JN, England.
I, the undersigned, hereby declare that the equipment referred to herein conforms to the requirements of the ATEX Directive 94/9/EC and the following standards:-
EN 60079-0:2006, EN 60079-1:2007, EN 60079-7:2007, EN 60079-15:2005, BS 6121:1989, EN 50262:1998 (Amd 2001), EN 61241-0:2004, EN 61241-1:2004.
Dr Geof Mood - Technical Director - (Authorised Person)
DUBAI
• HOUSTON • NEWCASTLE • SINGAPORE • SHANGHAI • PUSAN • PERTH
www.cmp-products.com
Ca
bl
e
Co
nn
ec
to
rS
el
ec
tio
n
Ta
bl
e
Logo’s shown for illustration purposes only. Please check certification for details
CONDUIT
CONDUIT
GLAND
GLAND
TYPE
TYPE
A2FFC
A2FFC
Cable
Connector
Size
Entry
Thread
“C”
Min Entry
Thread
Length “E”
Max
Envelope
Diameter
“D”
Protrusion
Length
“F”
Diameter Of Cable
“A”
Typical Diameter Of
Armour Conduit
“B”
Ordering
Reference
(Brass Metric)
Cable
Connector
Weight
(Kgs)
Metric
ID
OD
ID
OD
20S16
M20 X 1.5
15.0
29.0
17.0
3.2
4.3
5.1
9.8
20S16A2FFC1RAC000
0.044
20S16
M20 X 1.5
15.0
29.0
17.0
3.2
5.8
6.8
9.0
20S16A2FFC1RA001
0.048
20S16
M20 X 1.5
15.0
29.0
17.0
3.2
6.6
7.8
11.6
20S16A2FFC1RAC004
0.05
20S16
M20 X 1.5
15.0
29.0
17.0
3.2
8.0
9.1
13.9
20S16A2FFC1RAC009
0.05
20S16
M20 X 1.5
15.0
29.0
17.0
3.2
8.1
9.5
13.0
20S16A2FFC1RAC010
0.05
20S16
M20 X 1.5
15.0
29.0
17.0
3.2
8.1
10.2
14.0
20S16A2FFC1RAC020
0.054
20S16
M20 X 1.5
15.0
29.0
17.0
3.2
8.1
10.9
15.9
20S16A2FFC1RAC025
0.054
20S16
M20 X 1.5
15.0
29.0
17.0
3.2
8.1
11.7
15.9
20S16A2FFC1RAC030
0.056
20S
M20 X 1.5
15.0
29.0
17.0
6.1
9.9
10.9
15.9
20SA2FFC1RAC025
0.057
20S
M20 X 1.5
15.0
29.0
17.0
6.1
11.7
13.0
16.0
20SA2FFC1RAC040
0.057
20S
M20 X 1.5
15.0
29.0
17.0
6.1
11.7
13.9
18.9
20SA2FFC1RAC045
0.059
20S
M20 X 1.5
15.0
29.0
17.0
6.1
11.7
14.7
18.7
20SA2FFC1RAC060
0.061
20
M20 X 1.5
15.0
34.0
21.0
6.5
14.0
13.0
16.0
20A2FFC1RAC040
0.057
20
M20 X 1.5
15.0
34.0
21.0
6.5
13.1
15.6
21.0
20A2FFC1RAC050
0.082
20
M20 X 1.5
15.0
34.0
21.0
6.5
14.0
16.9
20.5
20A2FFC1RAC066
0.086
20
M20 X 1.5
15.0
34.0
21.0
6.5
14.0
18.0
21.0
20A2FFC1RAC070
0.09
20
M20 X 1.5
15.0
34.0
21.0
6.5
14.0
18.7
24.0
20A2FFC1RAC075
0.09
20
M20 X 1.5
15.0
34.0
21.0
6.5
14.0
20.0
23.5
20A2FFC1RAC080
0.095
20
M20 X 1.5
15.0
34.0
51.0
6.5
14.0
20.5
27.0
20A2FFC1RAC085
0.095
25
M25 X 1.5
15.0
44.0
25.0
11.1
15.3
17.6
25.0
25A2FFC1RAC100
0.115
25
M25 X 1.5
15.0
44.0
25.0
11.1
18.7
20.7
26.0
25A2FFC1RAC105
0.115
25
M25 X 1.5
15.0
44.0
25.0
11.1
20.0
22.3
26.5
25A2FFC1AC110
0.115
25
M25 X 1.5
15.0
44.0
25.0
11.1
20.0
23.7
30.8
25A2FFC1RAC115
0.124
25
M25 X 1.5
15.0
44.0
25.0
11.1
20.0
25.1
29.0
25A2FFC1RAC120
0.124
25
M25 X 1.5
15.0
44.0
25.0
11.1
20.0
26.5
34.0
25A2FFC1RAC180
0.124
32
M32 X 1.5
15.0
45.5
29.0
17.0
26.0
28.1
32.0
32A2FFC1RAC250
0.182
32
M32 X 1.5
15.0
45.5
29.0
17.0
26.3
30.4
38.0
32A2FFC1RAC280
0.188
32
M32 X 1.5
15.0
45.5
29.0
17.0
26.3
35.0
43.0
32A2FFC1RAC290
0.188
40
M40 X 1.5
15.0
50.0
30.0
23.5
32.2
36.4
44.0
40A2FFC1RAC300
0.23
40
M40 X 1.5
15.0
50.0
30.0
23.5
32.2
40.0
48.0
40A2FFC1RAC380
0.23
50S
M50 X 1.5
15.0
50.0
30.0
31.0
38.2
46.5
58.7
50SA2FFC1RAC450
0.3
50S
M50 X 1.5
15.0
50.0
30.0
31.0
38.2
51.2
60.0
50SA2FFC1RAC500
0.3
50
M50 X 1.5
15.0
50.0
30.0
35.6
44.1
51.2
60.0
50A2FFC1RAC550
0.34
All dimensions in millimeters
TECHNICAL DATA
CABLE GLAND TYPE
: A2FFC
INGRESS PROTECTION
: IP66, NEMA 4X
PROCESS CONTROL SYSTEM
: BS EN ISO 9001
ISO/IEC 80079-34:2011
HAZARDOUS AREA CLASSIFICATION
ATEX CERTIFICATION No
: SIRA06ATEX1097X, SIRA07ATEX4326X
ATEX CERTIFICATION CODE
:
II 2/3 GD Ex d IIC, Ex e II, Ex nR II, Ex tD A21 IP66 - Equipment Zone 1, 2, 21 & 22,
Gas Groups IIA, IIB & IIC
IEC Ex CERTIFICATION No
: IEC Ex SIR.06.0040X
IEC Ex CERTIFICATION CODE
: Ex d IIC / Ex e II / Ex nR II, Ex tD A21 IP66
CSA CERTIFICATION No
: 1211841
CSA CERTIFICATION CODE
: Ex d IIC / Ex e II, Enclosure Type 4x
INSTALLATION INSTRUCTIONS
Installation should only be performed by a competent person using the correct tools. Spanners should be used for tightening. Read all instructions
before beginning installation.
SPECIAL CONDITIONS FOR SAFE USE
• The A2FFC shall only be used where the temperature, at the point of entry, is between -60°C and +130°C.
• The entry component threads may need additional sealing to maintain the ingress protection rating as applicable to the associated equipment to
which it will be attached.
• The A2FFC is only suitable for flexible conduit installations. Cables must be effectively clamped to prevent pulling or twisting.
0518
Registered Office: Glasshouse Street • St. Peters • Newcastle upon Tyne • NE6 1BS
Tel: +44 191 265 7411 • Fax: +44 191 265 0581
E-Mail: [email protected] • Web: www.cmp-products.com