Priority Control Devices such as a flow switch, an Aquastat or other

electronic controller can be used to prioritize the domestic water system over

the heating system

• Follow all local codes, or in the absence of local codes, follow the most recent

edition of the National Standard Code, ANSI Z21103

• This illustration is a concept design only The reference to the 1/8

th

hole

in check is only for the State of Massachusetts There are a wide variety

of variations to the application of controls and equipment presented

Designers must add all necessary safety and auxiliary equipment to conform

to code requirements and design practice For more details, contact the

manufacturer

NOTICE

120 VAC

switch or

outlet

Hot w

at

er outle

t

Unions

T-handle gas shutoff valve

Check valve

Electronically controlled

pump timer. Activates

every 6 hours for 60

seconds Wire to

product approved pump

Heating Coil

(used with air-handler)

Cold water supply

3-inch gas exhaust

vent (Discharge must

comply with local and

state codes) Cannot

be common vented

with other appliances

An approved temperature and pressure

relief valve. Tie to location approved by

local codes and must meet BTU rating of

water heater model used

Check valve will have

1/8-inch hole drilling

in clapper optional

Atmospheric

vacuum

breaker

Shutoff

valve

Pressure

gauge

Apply correct thermal

expansion tank-size

per application

Shutoff valves

Shutoff valves

Check valves

Cold w

at

er inle

t

Gas inle

t

Water

filter

Drain

plug

Thermostatic mixing valve

Hot water

supply and

return to

heating coil

System installed with reverse

acting aquastat to shut off fan.

Suggested but not required by

248 CMR
50’-0” maximum distance from

water heater to fan coil

(Developed length) Not including

coil in heating unit

NSF-61 product

approved pump

Automatic tempering device

must be installed below

the top of the water heater

as per manufacturer’s

recommendations

Piping loop

between water

heater and fan

coil shall be in

compliance with

248 CMR

Tempered water to

plumbing fixtures. Must

meet temperature

requirements of 248 CMR

All water piping should be insulated

in accordance with 780 CMR

(Massachusetts energy code)

-Dual-purpose hot water heating-

(Domestic and Space Heating):

Diagrammatic layout of radiant heating and domestic water heater per mass code

The recirculation pump is to provide no less than 2 GPM (7.5 L/min) and no more than 4 GPM (15 L/min)

through each activated unit in the system.

Installation

Installation Manual

Ball

Valve

Isolation

Valve