Installation installation manual, 3inch and 4 inch vent installations only – Takagi T-H3M-IN/OS User Manual

Page 18

background image

18

Page

Installation

Installation Manual

For multiple sidewall exhaust terminations, an exhaust

termination must be at least 1 ft (305mm) away from

another exhaust termination An exhaust termination

must also be at least 2 ft (610 mm) away from an inside

corner (If the adjacent wall is less than 2 ft (610 mm) of

length, the minimum required distance away from the

inside corner will be equal to the length of that adjacent

wall)

Exhaust

termination

Inside

corner

1 ft

(305 mm) min

2 ft

(610 mm) min

1 ft (305 mm)

min

For multiple, direct-vent sidewall terminations that

combine the intake and exhaust into a single penetration,

space each direct-vent termination at least 1 ft (305 mm)

away from each other, no matter the orientation A direct-

vent termination must also be at least 2 ft (610 mm) away

from an inside corner (If the adjacent wall is less than 2 ft

(610 mm) of length, the minimum required distance away

from the inside corner will be equal to the length of that

adjacent wall)

Combined

intake and

exhaust

termination

Inside

corner

1 ft

(305 mm) min

2 ft

(610 mm) min

1 ft (305 mm)

min

For direct-vent sidewall

terminations that use two

separate penetrations for

the intake and exhaust,

keep the termination

clearances shown in the

diagrams on the right

Exhaust

Intake

1 ft.

(305 mm)

min.

Exhaust

Intake

A

A

Exhaust

Intake

1ft. (305 mm)

min.

Exhaust

Intake

A

A

A: 0.5 ft. (159mm)

The clearance of A is recommended on the basis of the structure of the water heater

* 3inch and 4 inch vent installations only